Pag. 119 di 152
10.4.4 Service
configuration
This service makes use of the following output variables:
Peaks Recording Service – Output variables
Name
ID
Type
Description
System clock
UTC
FF80h
Unix Timestamp (ID 06h)
Unix Tim offset (ID 07h)
Unix Tim DST flag (ID 08h)
Date (ID 09h)
Time (ID 0Ah)
Date/Time (ID 0Bh)
System clock, UTC
System clock
WALL TIME
FF81h
Unix Timestamp (ID 06h)
Unix Tim offset (ID 07h)
Unix Tim DST flag (ID 08h)
Date (ID 09h)
Time (ID 0Ah)
Date/Time (ID 0Bh)
System clock, WALL TIME
Timezone name
FF82h
BYTE ARRAY (ID 05h)
ASCIIZ string
Name of timezone in use
Firmware version
FF83h
BYTE PAIR (ID 04h)
Unsigned integer, Unsigned integer
Firmware version in use
(Major version, Minor version)
Slave ID
FF84h
WORD (ID 01h)
(Unsigned integer)
Instrument slave ID (Modbus)
Serial number
FF85h
DOUBLEWORD (ID 02h)
(Unsigned integer)
Instrument serial number
Timezone index
FF87h
WORD (ID 01h)
(Unsigned integer)
Timezone index in use
No configuration parameters are required by this service because both
target registers
and
reference
registers
are allocated by a single descriptor that specifies the type of detection to be performed by the