background image

akse srl

    Via Aldo Moro, 39    42100  Reggio Emilia    Italy

Tel. +39 0522 924 244    Fax +39 0522 924 245    info@akse.it    www.akse.it  

P.I. 01544980350     R.E.A. 194296      Cap. Soc. Euro 85.800,00 i.v.     

COPYRIGHT

Electrex is a trademark of Akse S.r.l. All rights reserved.
It is forbidden to duplicate, adapt, transcript this document without Akse written 
authorization, except when regulated accordingly by the Copyright Laws.

WARRANTY 

This product is covered by a warranty against material and manufacturing defects for 
a period of 24 months period from the manufacturing date.
The warranty does not cover the defects that are due to: 
• Negligent and improper use  
• Failures caused by atmospheric hazards 
• Acts of vandalism 
• Wear out of materials
• Firmware upgrades
Akse reserves the right, at its discretion, to repair or substitute the faulty products   
The warranty is not applicable to the products that will result defective in consequence 
of a negligent and improper use or an operating procedure not contemplated in this 
manual. 

RETURN AND REPAIR FORMALITIES

  

Akse accepts the return of instruments for repair only when authorized in advance. 
The transport costs are at customer charge. 

RE-SHIPPING OF REPAIRED PRODUCT

  

The terms for re-shipment of repaired products are ex-works, i.e. the transport costs 
are at customer charge.
Products returned as detective but found to be perfectly working by our laboratories, 
will be charged a 

fl

 at fee to account for checking and testing time irrespective of the 

warranty terms.

SAFETY

 

This instrument was manufactured and tested in compliance with IEC 61010 class 2 
standards  for operating voltages up to 250 VAC rms phase to neutral. 
In order to maintain this condition and to ensure safe operation, the user must comply 
with the indications and markings contained in the following instructions: 

• When the instrument is received, before starting its installation, check that it 

is intact and no damage occurred during transport. 

• Before mounting, ensure that the instrument operating voltages and the 

mains voltage are compatible then proceed with the installation. 

• The instrument power supply needs no earth connection. 
• The instrument is not equipped with a power supply fuse; a suitable external 

protection fuse must be foreseen by the contractor. 

• Maintenance and/or repair must be carried out only by quali

fi

 ed, authorized 

personnel 

• If there is ever the suspicion that safe operation is no longer possible, the 

instrument must be taken out of service and precautions taken againstits 
accidental use. 

• Operation is no longer safe when:

1) There is clearly visible damage. 
2) The instrument no longer functions. 
3) After lengthy storage in unfavorable conditions. 
4) After serious damage occurred during transport

The instruments must be installed in respect of all the local regulations.

OPERATOR SAFETY

Warning:

 Failure to observe the following instructions may lead to a serious danger 

of death.

• During normal operation dangerous voltages can occur on instrument terminals 

and on voltage and current transformers. Energized voltage and current 
transformers may generate lethal voltages. Follow carefully the standard safety 
precautions while carrying out any installation or service operation.

• The terminals of the instrument must not be accessible by the user after the 

installation. The user should only be allowed to access the instrument front panel 
where the display is located.

• Do not use the digital outputs for protection functions nor for power limitation 

functions. The instrument is suitable only for secondary protection functions.

• The instrument must be protected by a breaking device capable of interrupting both 

the power supply and the measurement terminals. It must be easily reachable by 
the operator and well identi

fi

 ed as instrument cut-off device.

• The instrument and its connections must be carefully protected against short-

circuit.

Precautions:

 Failure to respect the following instructions may irreversibly damage to 

the instrument.

• The instrument is equipped with PTC current limiting device but a suitable external 

protection fuse should be foreseen by the contractor.

• The outputs and the options operate at low voltage level; they cannot be powered 

by any unspeci

fi

 ed external voltage.

• The application of currents not compatible with the current inputs levels will 

damage to the instrument.

READINGS

READINGS DISPLAYED
(The parameters available vary according to instrument con

fi

 guration)

U

f

I

P

Q

S

PF

Press to scroll readings

L-N

f

I

P

Q

S

PF

L-L

In

P Avg

Q L Avg

S Avg

THD L-N

THD

P MD

Q C Avg 

S MD

THD L-L

I Avg

Q L MD

I MD

Q C MD

READINGS DISPLAYED
(The parameters available vary according to instrument con

fi

 guration)

Press to change readings

Press for 2 

seconds

Ea 

Er L 

Er C 

Es 

Ea 

 

E

2

Er L 

 

E

2

Er C 

 

E

2

Es 

 

E

2

CNT 

CNT 

E

2

TIME 

TIME 

E

2

LEGEND OF PARAMETERS AND SYMBOLS

L-N

Phase Neutral

U

Voltage

L-L

Phase Phase

I

Current

THD

Total Harmonic Distortion

In

Neutral current

Avg

Average (rolling) value

P

Active Power

MD

Maximum Demand

Q

Reactive Power

L

Inductive

S

Apparent Power

C

Capacitive

PF

Power Factor

TIME 

Life Time (total) (hour/100)

Ea

Active Energy

TIME 

E

2 Life Time (partial) (hour/100)

Er

Reactive Energy

CNT 

Pulse count (total)

Es

Apparent Energy

CNT 

E

2 Pulse count (partial)

f

Frequency

Further documentation may be downloaded from our web site www.electrex.it.

This document is owned by company AKSE that reserves all rights. 

DECLARATION OF CONFORMITY

 

Akse hereby declares that its range of products complies with the following directives 
EMC 89/336/EEC     73/23CE     93/68 CE   and complies with the following product’s 
standard CEI EN 61326 – IEC 61326    CEI EN 61010 – IEC 1010. 
The product has been tested in the typical wiring con

fi

 guration and with peripherals 

conforming to the EMC directive and the LV directive. 
Subject to modi

fi

 cation without notice. Preliminary. Edition 18-02-2008.

!

ZEPTO 96

INSTALLATION INSTRUCTIONS

MECHANICAL CHARACTERISTICS

Enclosure

Self-extinguishing plastic material class V0

Protection degree

IP40  on front panel, IP20 terminals side

Dimensions

105 x 90 x 58 mm (6 DIN modules)

VOLTAGE INPUT

Direct

Up to 300 Vrms phase-neutral
or 519 Vrms phase to phase

With external PT(VT)

Primary: programmable (max. 400 kV)
Secondary: programmable (max. 300 V)
Overload: 900 Vrms phase to phase for 1 sec

Power supply

230//- 10% 50/60Hz

Self consumption

< 3VA

MODELS

PFA8C11-02

ZEPTO 96 RS485 230-240V
ENERGY ANALYSER

PFA8C11-12

ZEPTO 96 RS485 230-240V 1DI 2DO
ENERGY ANALYSER

Reviews: