4
GB-
Vented Systems:
• circulation pump,
• pump valves,
• F & E tank,
• magnetic filter,
• automatic by-pass, if required.
Unvented Systems:
• circulation pump,
• pump valves,
• magnetic filter,
• automatic by-pass, if required,
• EHC sealed system kit,
• Automatic air vent,
• Twin Channel Heat Pack, if required.
Instructions and Building Regulations
This appliance must be fitted in accordance with the following
instructions.
The Local Building Regulations.
The Building Regulations.
The Building Standards, (Scotland-consolidated) Regulations.
Local water bylaws.
British Standards code of practice.
BS EN 12828:2003
Heating systems in buildings. Design for water-based heating
systems
BS EN 12831:2003
Heating systems in buildings. Method for calculation of the
design heat load
BS EN 14336:2004
Heating systems in buildings. Installation and commissioning of
water based heating systems
BS 7671:2008
Requirements for electrical installations. IEE Wiring Regulations.
Seventeenth edition
BS EN 13831:2007
Closed expansion vessels with built-in diaphragm for installation
in water
C.O.S.H.H.
Materials used in the manufacture of this appliance are non-
hazardous and no special precautions are required when fitting
or servicing this appliance.
PREPARATION
1. Load Check
A load check should be taken into consideration when
installing high output kW boilers.
2. Boiler location
The boiler must be fitted on a wall that will provide an
adequate fixing, and should be fitted in a location that the
boiler and pipe-work are not subject to frost and damp
conditions.
3. Central heating (design & installation)
Detailed recommendations are given in BS EN 12828:2003,
BS 6700: 2006+A1: 2009 and CP 342-2:1974
Pipes forming part of the useful heating surface should be
insulated to prevent any potential heat loss or frost damage
(BS 6700:1997).
Drain valves should be fitted at the lowest point of the system
pipe work in an accessible position.
Drain valves should be in accordance with BS 2879: 1980
and copper tube to BS EN 1057: 1996. is recommended.
LOCATION
The boiler can be installed in almost any location within a do-
mestic or commercial property, however consideration should be
given to future maintenance. Never leave the boiler switched off
if there is a danger of having temperatures below 0°C in the room
where it is located.
We recommend that a minimum clearance of 400 mm should
be allocated for: the removal of the front cover, adequate access
to the boiler plumbing and the internal electrical connections. A
50 mm allowance should be made at either side of the boiler to
allow free flow air into the boiler case and allow access to screws
on the boiler case.
THE BOILER MUST BE INSTALLED IN THE UPRIGHT POSI-
TION, FAILURE TO DO SO WILL INVALIDATE THE WARRAN-
TY
Summary of Contents for SlimJim
Page 2: ......