WARNINGS 

 

 

Not to be connected to control equipment that uses or generates more than 12VDC for 

Model 2110EX-12 or 24VDC for Model 2110EX-24 with respect to earth ground. 

 

The 2110EX must be installed, operated, and maintained only by qualified personnel, in 

accordance to relevant national/international installation standards (National Electric Code 

(NFPA, Article 504) and ANSI/ISA – RP12.6). 

 

Particular care shall be given to segregation and clear identification of IS conductors from 

non-IS conductors. 

 

De-energized power source (turn off power supply voltage) before installing or removing 

the connections when installed in Hazardous Area/Hazardous Locations or unless area is 

known to be non-hazardous. 

 

Warning: substitution of components may impair Intrinsic Safety. 

 

Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, 

disconnect power before servicing or unless area is known to be non-hazardous. 

 

The unit cannot be repaired by the end user and must be returned to the manufacturer or 

authorized representative. Any unauthorized modification must be avoided and will void any 

warranty. 

 

Note: X1-L3 and X1-L4 inputs are not reverse polarity protected. If reverse polarity occurs the unit 

will fail-safe by blowing the fuses. To avoid this situation, special care is required at installation. 

 

AVERTISSEMENTS

 

 

Ne doit pas être connecté à un équipement de contrôle qui utilise ou génère plus de 12 VCC 

pour le modèle 2110EX-12 ou 24 VCC pour le modèle 2110EX-24 par rapport à la terre. 

 

Le 2110EX doit être installé, utilisé et entretenu uniquement par du personnel qualifié, 

conformément aux normes d'installation nationales / internationales (National Electric Code 

(NFPA, Article 504) et ANSI / ISA - RP12.6). 

 

Une attention particulière doit être accordée à la séparation et à l'identification claire des 

conducteurs IS des conducteurs non IS 

 

Source d'alimentation hors tension (couper la tension d'alimentation) avant d'installer ou de 

retirer les connexions lorsqu'elles sont installées dans des zones dangereuses / endroits 

dangereux ou à moins que la zone ne soit reconnue comme non dangereuse. 

 

Avertissement: la substitution de composants peut compromettre la sécurité 

intrinsèque. 

 

Risque d'explosion: pour éviter l'inflammation des atmosphères inflammables ou 

combustibles, déconnectez l'alimentation avant l'entretien ou à moins que la zone ne 

soit reconnue comme non dangereuse. 

 

L'appareil ne peut pas être réparé par l'utilisateur final et doit être renvoyé au fabricant ou à 

un représentant autorisé. Toute modification non autorisée doit être évitée. 

 

Remarque: Les entrées X1-L3 et X1-L4 ne sont pas protégées contre l'inversion de polarité. Si 

l'inversion de polarité se produit, l'unité sera en sécurité en soufflant les fusibles. Pour éviter cette 

situation, une attention particulière est requise lors de l'installation. 

 

 

Summary of Contents for 2110EX-12

Page 1: ...EL 29132 Version V 002 Last Updated 01 2022 2022 Electrolab Inc All Rights Reserved USER MANUAL Explosion Proof Housing Digital Model 2110EX 12 and Model 2110EX 24 Standard and HLS Versions ...

Page 2: ...rdance with the terms andconditions of the License Agreement between the user and Electrolab Inc Electrolab Inc makes no representations of warranties with respect to the contents hereof and specificallydisclaims any implied warranties of merchantability of fitness for any particular purpose Electrolab Inc reserves the right to revise this publication and to make changes from time to time in its c...

Page 3: ...with certified Explosion Proof conduit or certified Explosion Proof cable and connector eg CLX and TMCX products Always attach the cables to the connector strain relief plate with cable ties This will ensure that cables do not migrate in the enclosure if they are disconnected from connector by accident Always lock the cover by fastening its hex screw with a hex socket use a hex spanner of 1 5mm AV...

Page 4: ...for Use in Hazardous Classified Locations UL61010 1 Standard for Safety Electrical Equipment For Measurement Control and Laboratory Use CSA C22 2 No 30 Explosion proof enclosures for use in Class I hazardous locations CSA C22 2 No 61010 1 Safety requirements for electrical equipment for measurement control and laboratory use UL 913 Standard for Intrinsically Safe Apparatus and Associated Apparatus...

Page 5: ...TERMINAL CONNECTIONS Table 1 EXPLOSION PROOF CONNECTION INTRINSICALLY SAFE CONNECTION X1 L1 VDC X1 L2 DC_GND X1 L3 Tx Rx X1 L4 Tx Rx X2 L1 HI X2 L2 SW X2 L3 HI HI X2 L4 SW J1 1 Tx Rx J1 2 DC_GND J1 3 Tx Rx J1 4 VDC J2 1 DC_GND J2 2 DC_GND J2 3 HI HI J2 4 HI ...

Page 6: ...ax J3 3 Uo Voc 10 71 V Ui Vmax J2 1 thru J2 4 Io Isc 18 03 mA Ii Imax J2 1 thru J2 4 Po 0 048 W Pi Pmax J2 1 thru J2 4 Co Ca 66 µF Ci Ci device C cable J2 1 thru J2 4 Lo La 4 mH Li Li device L cable For installation in which both Ci and Li of the Intrinsically Safe Apparatus exceed 1 of the Co and Lo parameters of the Associated Apparatus excluding cable then 50 of Co and Lo parameters are applica...

Page 7: ...uired at installation AVERTISSEMENTS Ne doit pas être connecté à un équipement de contrôle qui utilise ou génère plus de 12 VCC pour le modèle 2110EX 12 ou 24 VCC pour le modèle 2110EX 24 par rapport à la terre Le 2110EX doit être installé utilisé et entretenu uniquement par du personnel qualifié conformément aux normes d installation nationales internationales National Electric Code NFPA Article ...

Page 8: ...ith any orientation over the entire ambient temperature range 2 Use only explosion proof conduit or explosion proof cable to connect to the enclosure in accordance with relevant national international standards National Electric Code NFPA Article 504 3 Conduit seal is required within 18 inches of enclosure 4 Electrical connection of conductors up to 1 5 mm2 are accomodated by polarized plug in rem...

Page 9: ... BY STEP INSTALLATION INSTRUCTIONS 1 Check device for proper model and voltage a Review the model number on the attached label and compare to the site power requirements Example of a 24v Label b Open the enclosure and observe the voltage marked on the label placed on the inside wall of the enclosure base Make sure the voltage matches the model number and the location voltage requirements Example o...

Page 10: ...ensor connections shown at right Tighten connector 6 Unscrew the bottom part of the union from the 2110EX Then screw the bottom part of the union s 1 inch FNPT onto the sensor s 1 inch MNPT flange until hand tight Make sure the connector cable is not caught in the threads or joint Tighten the union using a 1 5 wrench but do not overtighten Ensure cable is not caught in threads or joint 7 Screw tog...

Page 11: ... drawing 2110EX 002_RevA following the pinout that is marked on the circuit board The wire size should be in the range 14 to 28 AWG Secure the wires on the pull tab using a cable tie 9 Repeat step 8 for the gray HLS switch connector X2 if the 2110EX has the HLS option 10 Seal the incoming conduit with a certified EX fitting within 18 inches from the 2110EX enclosure ...

Page 12: ...USER MANUAL Page 12 of 16 Document EL29132 Version V 002 Control Drawing ...

Page 13: ...USER MANUAL Page 13 of 16 Document EL29132 Version V 002 ...

Page 14: ...USER MANUAL Page 14 of 16 Document EL29132 Version V 002 ...

Page 15: ...USER MANUAL Page 15 of 16 Document EL29132 Version V 002 ...

Page 16: ...USER MANUAL Page 16 of 16 Document EL29132 Version V 002 For more information contact Electrolab Electrolab Inc 159 Enterprise Parkway Boerne Texas 888 301 2400 www electrolabcontrols com ...

Reviews: