SERVICE MANUAL Blast Chiller Freezer 100 - 200
Parameter
ID
Parameter
Description
Table
Min
Max Default
199
HAC
Cavity High temperature threshold: the warning is triggered if
Cavity Temperature > (Cavity Set + HAC). Valid only for holding
cycles.
-50
125
5
200
LAC
Cavity Low temperature threshold: the warning is triggered if
Cavity Temperature < (Cavity Set - LAC). Valid only for holding
cycles.
-50
125
5
201
Afd
Cavity High/Low temperature differential: the High temperature
warning is resettled if Cavity Temperature is less or equal than
(Cavity Set + HAC - Afd).
Low Temperature warning is resettled if Cavity Temperature is
greater or equal than (Cavity Set - LAC + Afd)
-50
125
1
202
bCoF
enables/disables the fan to cooling eletronic boards
{0, “Disabled”}
{1, “Enabled"}
0
1
1
203
ERLO
External resistor load to be used for energy consumption calcu-
lation. [ohm]
0 50000
0
204
NVOL
Nominal appliance voltage supply. Used for energy consump-
tion calculation (heaters) [V]
0
500
230
205
POFF
Power cunsumption offset . Used for energy consumption calcu-
lation [W]
0 50000
0
206
REm
Defines if the cooling unit is remote or on board
{0, “On board”}
{1, “Remote"}
0
1
0
207
APPM
Appliance model
{0, "LW 30 Kg"}
{1, "LW 50 Kg"}
{2, "LW 70 Kg"}
{3, "LW 100 Kg"}
{4, "LW 150 Kg"}
{5, "LW 200 Kg"}
0
5
0
208
APPT
Appliance type: defines if the appliance is only a blast chiller
(BC) or a blast chiller and freezer (BCF)
{0, "BC"}
{1, "BCF"}
0
1
1
210
dEMo
Enables/disables different demo modes.
· Disabled: the appliance behaves normally;
· Basic: the appliance simulates the normal behaviour. All tem-
peratures are internally simulated, there is no need of an ACU
connection;
· Exhibition: the appliance simulates the normal behaviour ex-
cept the door sensing which is retrieved from real sensor ;
· Development: all the appliance features are simulated. Tem-
peratures and digital inputs are sent to target through a serial
port
{0, “Disabled”}
{2, “Exhibition”}
{3, “Development”}
{4, “Remote view”}
0
4
0