16
Installation manual
5.5
Shared exhaust duct
It is recommended that each machine is connected to a separate exhaust duct.
When several machines shall use the same exhaust duct the exhaust duct must increase after each machine. The
recommended diameter increase progression is the one in the table.
If several machines are installed on the same exhaust pipe, it is recommended to adjust the airflow on the machines
when all machines are started and running a program with no heat.
Please consider that unnecessarily large ducts create issues with the draught.
fig.W00198
Number of machines
1
2
3
4
Exhaust m
3
/h
140
280
420
560
⌀
mm
100
100
100
100
Fresh air inlet cm
2
300
400
600
800
Exhaust duct length 0–6 m
⌀
mm
100
100
160
160
Exhaust duct length 6–50 m
⌀
mm
If the exhaust duct length exceeds 6 m the diameter must be increased.
100
160
200
200
The exhaust duct diameter must not be reduced.
5.6
Exhaust dimensioning
It is important that the machine has correct air volume compared to each machines power.
If the air flow is smaller or larger this will result in a longer drying period.
If the outlet pipe is long or the ventilation is not properly designed we recommend to clean the outlet pipes periodi-
cally. Usually, longer ducts need more frequent cleaning.
The exhaust pipes shall be short in order for the machine to work in the best way.
All cover panels must be mounted in order for the machine to work in the best way.