16
INSTALLING THE COOKER HOOD
Ducting Connection
Connect the ducting chosen to:
• the Ø150mm ducting spigot on top of the motor
housing, or the Ø150-120mm ducting spigot
item
9
and secure using the jubilee clips
item
25
.
• A Ø120-125mm collar
item
9.1
is provided to
fi
t over
the Ø120mm ducting spigot when 125mm ducting is
fi
tted.
If the room where the cooker hood is to be used
contains a fuel burning appliance such as a central
heating boiler, then its
fl
ue must be of the room
sealed or balanced
fl
ue type.
If other types of
fl
ue or appliances are
fi
tted sure
that there is an adequate supply of air to the
room.
The cooker ducting (extraction mode) must never
be connected to central heating
fl
ues, radiators or
water heaters etc.
Recirculation
The cooker hood is supplied speci
fi
ed for use in the
recirculation mode, with the charcoal
fi
lter
fi
tted.
In the recirculation mode contaminated air is passed
through the charcoal
fi
lter to be puri
fi
ed and recirculated
into the kitchen through the grille outlets on either side
of the chimney.
Recirculation Connection
• Fix the connection
item
15
to the frame using the 4
screws provided
.
• Fix the
fl
ange
item
10
to the lower opening of the
connection
item
15
.
• Connect the hood air outlet to the
fl
ange in the lower
part of the junction using a rigid or
fl
exible ø 150
tube (by installer’s choice).
9
ø 150
ø 125
25
25
9.1
15
10