Doc. No:
560001 EG
Page:9
Ed.1" 08-2014
From ser. no.:
To manually activate a defrost cycle it is necessary to keep the tem-
perature decrease button pressed for at least 3 seconds.
The display shows the message
dFb/
defrost
start
for a few seconds
and the icon signalling activation of the defrost cycle lights up.
Defrost can be manually stopped by pressing the DEF/decrease tem-
perature button again for at least 3 seconds. The display shows the
message
dFE
/defrost
end.
Defrost in the range models is carried out following the algorithm va-
lues: 1) parameter
dF0,
associating the actual hours of compressor
operation, 2) parameter
dF1,
number of door openings, where para-
meter
dF0
must be reduced ,3)parameter
dF2,
minutes to be add to
parameter
dF1
from subtracted to parameter
dF0,
to anticipate defrost
.
Parameter
dl
remains active if these values are not respected.
In case of activation of continuous cycle, by pressing the temperature
decrease button for more than 5 seconds the display will show the
message
ccb,
at the same time as the temperature the message
tc
will appear, meaning that “turbo cooling” has been activated. The cycle
will end for time, by parameter
CC
, or for temperature by parameter
AL
, or by pressing the button again.
The humidity value is activated by pressing the corresponding button.
Three modes can be activated: low, medium, high %
.F0= 3
The function activates the evaporator fans following the logic of low,
medium and high humidity % to be obtained in the compartment.
The parameters functioning in this are:
MANUAL DEFROST
ACTIVATION OF “TURBO CO-
OLING” CONTINUOUS CYCLE
ccb
ACTIVATION OF HUMIDITY
CYCLE
SERVICE ALARMS AND SIGNALLING
DFb dFE
ccE
tC
Selection
Correspondence
Low humidity
Medium humidity
High humidity
Fans always ON
Fans always ON
Fans always ON
F11= Fans ON
F12= Fans Off
F13= Fans ON
F14= Fans Off
F15= Fans ON
F16= Fans Off
Compressor OFF
Compressor ON
Evaporator fans functionality