DIGITAL TEMPERATURE MONITOR – MASTERTEMP
10
Rev
1.1
Continuation.... MASTERTEMP CONFIGURATION MENU CONFI
Submenu
Parameters
Variable
Description
Sensor
Readout
Sensor 1
Sensor 2
Winding 1
Winding 2
Winding 3
ON / OFF
Menu for enable or disable the sensors input 1 and 2 and CTs 1, 2 and 3.
Note 1: When turning off Sensor 2, the Type Readout automatically changes to BKP.
Note 2: It’s not possible to disable Sensor 1 and Sensor 2 simultaneouly.
LCD
Display
Setup
Contrast
0 to 20
Adjusts the display contrast.
Back Light
ON / OFF
It turns on or off the display backlight.
RS485
Output
Setup
Protocol
MBUS
DNP
Configures the type of protocol:
MBUS – Modbus RTU
DNP – DNP 3 L2
Address
1 to 254
Configuration for the serial net address
Each equipment connected to the net RS485 (pins 20 and 21) must have an unique
address, different from other equipment so the Supervisory System can identify it.
BaudRate
kbps
Auto
2.4
4.8
9.6
19.2
38.4
57.6
AUTO – Automatically detects the communication speed;
2.4 – Sets the communication speed in 2400 bps;
4.8 – Sets the communication speed in 4800 bps;
9.6 – Sets the communication speed in 9600 bps;
19.2 – Sets the communication speed in 19200 bps;
38.4 – Sets the communication speed in 38400 bps;
57.6 – Sets the communication speed in 57600 bps.
Parity
ODD
EVEN
NONE
Parity configuration, the last bit to be transmitted in the message to verify the
data integrity.
ODD – Last bit of the message is 1;
EVEN – Last bit of the message is 0;
NONE – No parity.
Protection Net
ON
OFF
Configuration of the serial net protection:
OFF – Protection system against parameters change OFF. Parameters
modification is allowed through the serial net.
ON – Protection system against parameters change ON. Parameters
modification is not allowed through serial net, only readings.
Current
Outputs
Scale
0-1 mA
0-5 mA
0-10 mA
0-20 mA
4-20 mA
0-1 mA – sets the current output for 0 to 1 mA;
0-5 mA – sets the current output for 0 to 5 mA;
0-10 mA – sets the current output for 0 to 10 mA;
0-20 mA – sets the current output for 0 to 20 mA;
4-20 mA – sets the current output for 4 to 20 mA.
Cur 1 output
range
Min out 1
-50 to 250
°C
Configures the temperature range to the current output 1 (Sensor 1).
Min out 1: temperature value equivalente to the minimum level of analog
scale (4 mA if selected scale is 4 – 20 mA)
Max out 1: temperature value equivalente to the maximum level of analog
scale (20 mA if selected scale is 4 – 20 mA)
Max out 1
-50 to 250
°C
Cur 2 output
range
Min out 2
-50 to 250
°C
Configures the temperature range to the current output 2 (Sensor 2).
Min out 2: temperature value equivalente to the minimum level of analog
scale (4 mA if selected scale is 4 – 20 mA)
Max out 2: temperature value equivalente to the maximum level of analog
scale (20 mA if selected scale is 4 – 20 mA)
Max out 2
-50 to 250
°C
Summary of Contents for MASTERTEMP
Page 1: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 1 Instructions Manual Manual de Instruções ...
Page 7: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 4 APPLICATION EXAMPLE ...
Page 8: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 5 CATALOG CODE DIMENSION ...
Page 9: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 6 WIRING DIAGRAM MASTERTEMP ...
Page 45: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 42 EXEMPLO DE APLICAÇÃO ...
Page 46: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 43 CÓDIGO DE CATÁLOGO DIMENSÕES ...
Page 47: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 44 DIAGRAMAS DE LIGAÇÃO MASTERTEMP ...