DIGITAL TEMPERATURE MONITOR – MASTERTEMP
14
Rev
1.1
Continuation.... MASTERTEMP CONFIGURATION MENU ACTUA
Submenu
Parameters
Variable
Description
Shutdown
Setup
Due Load
ON
OFF
Enables or Disables the actuation due load percentage.
ON –
Enables the shutdown by load.
OFF
– Disables the shutdown by load.
Winding 1
Winding 2
Winding 3
50 to 200%
Configuration of percentage load to the shutdown for
each winding.
Due
Temperature
Oil
Winding 1
Winding 2
Winding 3
-50 to 250°C
Configuration of temperature to the shutdown for oil
and each winding.
Delay
0 to 20 min
Configuration for the delay time to shutdown in
minutes. When the operation temperature (or load)
reaches the set temperature (or load), the IDE starts to
count and shutdown the transformer case the read
value keeps above the preset limit. If preset value is 0
(zero), the shutdown is actuated immediately.
Cooling
Due Load
ON / OFF
Enables or disables the cooling groups due load.
ON –
Enables the cooling actuation due load
OFF
– Disables the colling actuation due load
Winding 1
1° Group
50 to 200%
Configuration of percentage load to start the cooling.
2° Group
50 to 200%
Winding 2
1° Group
50 to 200%
2° Group
50 to 200%
Winding 3
1° Group
50 to 200%
2° Group
50 to 200%
Due
Temperature
Oil
1° Group
-50 to 250 °C
Configuration of temperature to start the cooling.
2° Group
-50 to 250 °C
Winding 1
1° Group
-50 to 250 °C
2° Group
-50 to 250 °C
Winding 2
1° Group
-50 to 250 °C
2° Group
-50 to 250 °C
Winding 3
1° Group
-50 to 250 °C
2° Group
-50 to 250 °C
Histeresys
0 to 30 °C
Temperature difference for the deactivation of the
cooling.
Exemple
: If the cooling value is set to 65 °C and the
histeresys to 5 °C, the cooling will be deactivated
when temperature reaches 59.9 °C. This parameter is
valid for the 2 cooling groups.
Invertion
Disable
Enable
Simultaneous
Configuration of automatic invertion for the cooling
groups.
Disable –
the cooling groups invertion is off.
Enable –
the cooling groups invertion is enabled.
There is an alternation for each start up. The
cooling group previously stopped is started up.
Simultaneous –
The start up is for both cooling
groups.
Summary of Contents for MASTERTEMP
Page 1: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 1 Instructions Manual Manual de Instruções ...
Page 7: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 4 APPLICATION EXAMPLE ...
Page 8: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 5 CATALOG CODE DIMENSION ...
Page 9: ...DIGITAL TEMPERATURE MONITOR MASTERTEMP 6 WIRING DIAGRAM MASTERTEMP ...
Page 45: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 42 EXEMPLO DE APLICAÇÃO ...
Page 46: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 43 CÓDIGO DE CATÁLOGO DIMENSÕES ...
Page 47: ...MONITOR DIGITAL TEMPERATURE MASTERTEMP 44 DIAGRAMAS DE LIGAÇÃO MASTERTEMP ...