CREATED ON: June 21, 2016
Keys and Operation
RUN Mode
1. On power application, relay will be in NC condition for
approximately 10sec.
2. During healthy condition, all the voltage parameters shall be
displayed with instantaneous values. Relay and relay LED will
be in ON or OFF condition depending on Rly ’y’ or Rly ‘n’ setting.
3. During fault condition, type of fault shall be displayed with
Relay OFF or ON Status depending on Rly ’y’ or Rly ‘n’ setting.
Auto mode
4. Once the fault is recovered, unit automatically comes back
to parameter display mode as mentioned in point – 2.
Manual mode
5. Once the fault is recovered, manual key to be pressed to
bring back display mode as mentioned in point – 2.
6. If faults are rectified before set trip delay timings of relay,
display will continue to show fault status. Relay status remain
unaltered. Press Manual key to show the parameter display.
Press MENU/ENTER key for 3Seconds to HOLD/SCROLL display.
When fault occurs unit display’s the following:
Parameters
Top
display
Bottom
display
OVER VOLTAGE
Err
OUOL
UNDER VOLTAGE
Err
UUOL
OVER CURRENT
Err
OCrt
UNDER CURRENT
Err
UCrt
OVER FREQUENCY
Err
O-HZ
UNDER FREQUENCY
Err
U-HZ
EARTH LEAKAGE
Err
ELr
PHASE UNBALANCE
Phs
UbAL
PHASE REVERSE
Phs
rEU
R PHASE FAIL
FAIL
P-r
Y PHASE FAIL
FAIL
P-y
B PHASE FAIL
FAIL
P-b
MENU/ENTER/HOLD/SCROLL Key
RUN Mode
: Used to select scroll/hold the
parameters.
PROGRAM MODE
: Used to enter into program
mode.
: used to select next parameters.
INC Key
PROGRAM Mode
: Used to increase the values.
DEC Key
PROGRAM Mode
: Used to decrease the values.
MANUAL/ESC Key
RUN Mode
: When fault recovery happens this
key shall be used to Load ON/OFF manually.
PROGRAM Mode
: It is used to view the previous
parameters.
Phase Unbalance Condition
To set unbalance condition for 20%.
Set 20 in unit (PUbL=20 as shown in the table).
If RY=350V, YB=450V, BY=319V in the load.
Fault is created in the unit, upper displays shows “Phs” and
lower shows “UbAL”.
Calculations are as follows
Set nVOL=415V, PUbL=20% in the unit.
Vry=350V, Vyb=450V, Vbr=319V, Vavg= 373V
Vry -Vavg=23V, Vyb -Vavg=77V, Vb-Vavg=54V
Phase unbalance= (Maximum deviation / Vavg) * 100
= (77/373)*100= 20 %
PROGRAM Mode
To enter program mode press INC & DEC key simultaneously for 4sec.
Programming
Parameters
Range
Factory
setting
1
“nUOL”
Nominal voltages: 415V
415
2
“OUOL”
Over Voltage. Range: 5 to 100V
030
3
“UUOL”
Under voltage. Range: 5 to 100V
030
4
“CT-P”
CT Primary. Range: 5 to 2500A
005
5
“nCrt”
Nominal Current. Range: 0.5-500A
005.0
6
“OCrt”
Over Current. Range: 105-800%
120
7
“UCrt”
Under Current. Range: 20-95%
20
8
“
PUbl”
Phase Unbalance. Range: P 1-20%
20
9
“O-Hz”
Over frequency. Range: 2 to 5Hz
05
10
“U-Hz”
Under frequency. Range: 2 to 5Hz
05
11
“ELr”
Earth leakage current. Range: 1 to 8A
1
12
“IrdY”
Inrush delay. Range: 1-60sec
01
13
“ tdOU”
Trip delay Over Voltage. Range: 1- 250sec
005
14
“ tdUU”
Trip delay Under Voltage. Range: 1 - 250sec
005
15
“ tdOC”
Trip delay Over Current. Range: 1 - 250sec
005
16
“ tdUC”
Trip delay Under Current. Range: 1 - 250sec
005
17
“tdUb”
Trip delay Unbalance. Range: 1 – 250sec
005
18
bYPS
“OUL Y/n”
Bypass Over Voltage
n
19
bYPS
“UUL Y/n”
Bypass Under Voltage
n
20
bYPS
“OCt Y/n”
Bypass Over Current
n
21
bYPS
“UCt Y/n”
Bypass Under Current
n
22
bYPS
“UBL Y/n”
Bypass Phase Unbalance
n
23
bYPS
“OHz Y/n”
Bypass Over Frequency
n
24
bYPS
“UHz Y/n”
Bypass Under Frequency
n
25
CntL
rLY ‘n’
Relay & Status LED OFF in
healthy condition
y
rLY ‘Y’
Relay & Status LED ON in
healthy condition
26
“Auto”
rst ‘Y’
Auto reset enable
“Y”
rst ‘n’
Auto reset disable
(Manual mode)
“n”
Technical Specification
Disposition
Once the product life is over, you may send back the
unit to EAPL for disposition
Contact
Electronic Automation Pvt. Ltd
#20, KHB Industrial Area
Yelahanka, Bangalore -560064
Ph: +91-80-28567561/2, /42802345
Email:
info@eaplindiamail.com
,
www.eaplindia.com
Function
Phase Unbalance, Phase
Reversal, Phase Failure, Under
and Over Voltage, Under and
Over Current, Under and Over
Frequency, Earth Leakage
Monitor and Control.
System Input
Input Voltage
415V AC(3Ph-4W)
Input Current
Current input (AR,AY,AB) Ib=5A
Input Frequency
50 Hz,
±
10%
Control output
1c/o rated for 10A @
250VAC/28VDC resistive load
Power Consumption
5VA/ 1W
Accuracy
Voltage
±
4V of display value
Current
±
5% of Ib
±
1 digit (Ib = 5A)
Frequency
±
2% of FS
±
1 digit
Trip Time
±
1% of set delay
±
2 sec
Earth leakage current
±
500mA of setting accuracy.
General
Minimum sensing current
0.5A
Maximum sensing current
5A(Above 5A> Ext.CT can be
used)
Earth leakage Trip time delay
5 sec Earth leakage
Phase Failure trip time delay
< 5 sec
Phase reverse trip time delay
Instantaneous
Frequency trip time delay
Instantaneous
Recovery Time
2 sec Min
Power On Delay
10 sec Max
Mode of Operation
Auto/ Manual
Core Balance Current
Transformer type
Toroidal core
CBCT Size Internal Diameter
100mm
Climatic
Ambient Temperature
Operation: -10
°
C to +55
°
C
Storage : -25
°
C to +80
°
C
Humidity
MAX 85% RH @ 40
°
C
OD RE NN 610002 REV 02/21-06-16