-22-
Operating instructions - main menu
Pressing the menu key will display the main menu page:
Each menu item is described below:
Use the arrow keys to scroll through to the menu item required and then press the enter key. Pressing the menu
key will always return the display to the previous screen until the normally displayed screen is reached.
The events logged in history will be displayed starting with the
event logged. Press the up arrow key to go
to the last event logged. Use the up / down arrow keys to scroll through all of the events recorded.
The system has a 999 log memory, once the memory is full new events will continue to be stored whilst the
oldest will be lost. History can be cleared using a PC running FireConfig.
User access level 2 is required. After entering the password press “ENTER” and the main menu will be
displayed but now you are at access level 2, press “ENTER” again for Isolate deisolate.
Use the left right arrow keys to select either
or
and press return.
Using the +/- keys enter the zone number to be isolated. Use the down arrow key to scroll to TIME MINS.
Using the +/- keys enter up to 240 minutes (4 hours), or leave at 000 (continuously isolated). Use the down
arrow key to scroll to ok and press return. The ISOL led should now illuminate and on the main page the
number of zones isolated should be indicated in the bottom right of the display.
Using the +/- keys enter the zone number to be isolated. Use the down arrow key to scroll to “OK” and press
return.
1. MAIN MENU > HISTORY
first
2. MAIN MENU > ISOLATE DE-ISOLATE
ISOLATE
DE-ISOLATE
ISOLATE
DEISOLATE
10:51 05/06/08
MAIN MENU
USER 1
1. HISTORY
8. REBOOT SYSTEM
2. ISOLATE DEISOLATE
9. LIVE VALUES
3. SETUP
10. CHANGE USER LEVEL
4. SYSTEM MENU
11. VIEW FAULTS
5. GAS DETECTION
12. VIEW PRE ALARMS
6. DELAYED ALARMS
13. VIEW ISOLATES
7. RETURN: MAIN MENU
10:51 05/06/08
ISOLATE ZONES
ZONES ISOLATED: 00
ISOLATE ZONE # 01
TIME MINS: 000
(MAX = 240, 000=CONTINUOUS)
OK
10:51 05/06/08
DEISOLATE ZONES
ZONES ISOLATED: 01
DEISOLATE ZONE # 01
OK
ED816A Addressable Fire and gas detection Installation manual 8-9-08 Rev-a