31
9. Power supply system
• Each power supply system for heating cables should be equipped with the
residual current device of the sensitivity
∆
Ł
30mA, for anti-shock
protection. One RCD device should protect electric circuits no longer than
500 m each.
• To protect the power supply system against short circuits, it is required to
apply type C characteristics circuit breakers.
• Application of contactors is recommended for the systems with large
current load. This will protect controllers and prolong fault-free operation
of those devices.
10. Check of the ready system
After the heating cable and thermal insulation have been laid, perform the
measurements of the heating cable insulation’s resistance, and test-run the
heating circuits to assess the correctness and safety of the system’s
operation.
The heating cable insulation’s
resistance, as measured with
an appliance of the rated
voltage 1000 V
(megaohmmeter),
should not drop below
50 M
Ω
.
Enter the results
into the
Warranty Card.