43
Instruction Manual
PSI 8000 3U Series
EN
Date: 05-03-2012
About the device
2.2 Device specifications
PSI 8040-170 3U PSI 8080-170 3U PSI 8200-70 3U
PSI 8500-30 3U PSI 8040-340 3U
Mains input
Input voltage range
340…460V AC
340…460V AC
340…460V AC
340…460V AC
340…460V AC
Input voltage range optional
-
-
-
-
-
Required phases
L1, L2, PE
L1, L2, PE
L1, L2, PE
L1, L2, PE
L1, L2, L3, PE
Input frequency
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
Input fuse
2x T16A
2x T16A
2x T16A
2x T16A
4x T16A
Input current
max. 11A
max. 16A
max. 16A
max. 16A
max. 29A
Power factor
> 0.99
> 0.99
> 0.99
> 0.99
> 0.99
Output - Voltage
Nominal voltage U
Nom
40V
80V
200V
500V
40V
Adjustable range
0V…U
Nom
0V…U
Nom
0V…U
Nom
0V…U
Nom
0V…U
Nom
Stability at mains fluctuation ±10%
∆
U
IN
< 0.02%
< 0.02%
< 0.02%
< 0.02%
< 0.02%
Stability at 0…100% load
< 0.05%
< 0.05%
< 0.05%
< 0.05%
< 0.05%
Ramp-up time 10...90% at 100% load
max. 30ms
max. 30ms
max. 30ms
max. 30ms
max. 30ms
Ripple @ BWL 20MHz
< 100mVpp
< 10mVrms
< 100mVpp
< 10mVrms
< 200mVpp
< 25mVrms
< 250mVpp
< 70mVrms
< 150mVpp
< 10mVrms
Accuracy*
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
10mV
10mV
100mV
100mV
10mV
Remote sense compensation
max. 2.5V
max. 2.5V
max. 6V
max. 10V
max. 2.5V
Overvoltage protection
threshold (adjustable)
0…44V
0…88V
0…220V
0….550V
0…44V
Output - Current
Nominal current I
Nom
170A
170A
70A
30A
340A
Adjustable range
0…I
Nom
0…I
Nom
0…I
Nom
0…I
Nom
0…I
Nom
Stability at mains fluctuation ±10%
∆
U
IN
< 0.05%
< 0.05%
< 0.05%
< 0.05%
< 0.05%
Stability at 0…100%
∆
U
OUT
< 0.15%
< 0.15%
< 0.15%
< 0.15%
< 0.15%
Ripple @ BWL 20MHz
< 528mApp
< 106mArms
< 300mApp
< 40mArms
< 44mApp
< 11mArms
< 14mApp
< 8mArms
< 600mApp
< 80mArms
Accuracy*
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
100mA
100mA
10mA
10mA
100mA
Transient recovery time 10….90% load
< 2ms
< 2ms
< 2ms
< 2ms
< 2ms
Output - Power
Nominal power P
Nom
3300W
5000W
5000W
5000W
6600W
Nominal power at derating
0...P
Nom
0...P
Nom
0...P
Nom
0...P
Nom
0...P
Nom
Accuracy*
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
0.001kW
0.001kW
0.001kW
0.001kW
0.001kW
Efficiency
93%
93%
95.20%
95.50%
93%
Miscellaneous
Ambient temperature
0….50°C
0….50°C
0….50°C
0….50°C
0….50°C
Storage temperature
-20….70°C
-20….70°C
-20….70°C
-20….70°C
-20….70°C
Humidity rel.
< 80%
< 80%
< 80%
< 80%
< 80%
Dimensions (WxHxD) **
19" 3U 595mm
19" 3U 595mm
19" 3U 595mm
19" 3U 595mm
19" 3U 595mm
Weight
19.8kg
19.8kg
19.8kg
19.8kg
25.5kg
Redundancy
no
no
no
no
yes
Isooutput to enclosure
500V DC
500V DC
500V DC
1000V DC
500V DC
Isolation -output to enclosure
Isolation input to output
Cooling
Safety
EMC standards
Overvoltage class
Protection class
Pollution degree
Operational altitude
Series operation
max. series connection voltage
Master-Slave
Parallel operation
max. parallel connection voltage
Master-Slave
Analogue programming
Input range
Accuracy
Input impedance
Article number
09230445
09230430
09230440
09230435
09230446
300V DC
4200V DC
by fans, air inlet on the front, air exhaust on the rear
EN 60950
EN 61326, EN 55022 Class B
2
1
2
<2000m
600V
no
≤
0.2%
53kOhm
1500V
yes, via Share bus
0…5V or 0…10V, selectable
* Related to the nominal value, the accuracy defines the maximum allowed deviation between set value and actual value.
Example: a 80V model has min. 0.2% voltage accuracy. This is 160mV. When setting a voltage of 5V and with an allowed maximum deviation of 160mV, the resulting
actual value could be between 4.84V and 5.16V.
** Enclosure dimensions only, not overall dimensions