44
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
EN
Instruction Manual
PSI 8000 3U Series
Date: 05-03-2012
About the device
PSI 8040-510 3U PSI 8080-340 3U PSI 8160-170 3U PSI 8200-140 3U PSI 8400-70 3U
Mains input
Input voltage range
340…460V AC
340…460V AC
340…460V AC
340…460V AC
340…460V AC
Input voltage range optional
-
-
-
-
-
Required phases
L1, L2, L3, PE
L1, L2, L3, PE
L1, L2, L3, PE
L1, L2, L3, PE
L1, L2, L3, PE
Input frequency
50/60Hz
50/60Hz
50/60Hz
50/60Hz
50/60Hz
Input fuse
6x T16A
4x T16A
4x T16A
4x T16A
4x T16A
Input current
max. 28A
max. 28A
max. 28A
max. 28A
max. 28A
Power factor
> 0.99
> 0.99
> 0.99
> 0.99
> 0.99
Output - Voltage
Nominal voltage U
Nom
40V
80V
160V
200V
400V
Adjustable range
0V…U
Nom
0V…U
Nom
0V…U
Nom
0V…U
Nom
0V…U
Nom
Stability at mains fluctuation ±10%
∆
U
IN
< 0.02%
< 0.02%
< 0.02%
< 0.02%
< 0.02%
Stability at 0…100% load
< 0.05%
< 0.05%
< 0.05%
< 0.05%
< 0.05%
Ramp-up time 10...90% at 100% load
max. 30ms
max. 30ms
max. 30ms
max. 30ms
max. 30ms
Ripple @ BWL 20MHz
< 150mVpp
< 10mVrms
< 150mVpp
< 10mVrms
< 300mVpp
< 30mVrms
< 200mVpp
< 25mVrms
< 300mVpp
< 40mVrms
Accuracy*
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
10mV
10mV
100mV
100mV
100mV
Remote sense compensation
max. 2.5V
max. 2.5V
max. 5V
max. 6V
max. 12V
Overvoltage protection
threshold (adjustable)
0…44V
0….88V
0….176V
0…220V
0…440V
Output - Current
Nominal current I
Nom
510A
340A
170A
140A
70A
Adjustable range
0…I
Nom
0…I
Nom
0…I
Nom
0…I
Nom
0…I
Nom
Stability at mains fluctuation ±10%
∆
U
IN
< 0.05%
< 0.05%
< 0.05%
< 0.05%
< 0.05%
Stability at 0…100%
∆
U
OUT
< 0.15%
< 0.15%
< 0.15%
< 0.15%
< 0.15%
Ripple @ BWL 20MHz
< 900mApp
< 120mArms
< 600mApp
< 80mArms
< 300mApp
< 60mArms
< 89mApp
< 22mArms
< 33mApp
< 9mArms
Accuracy*
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
100mA
100mA
10mA
100mA
10mA
Transient recovery time 10….90% load
< 2ms
< 2ms
< 2ms
< 2ms
< 2ms
Output - Power
Nominal power P
Nom
10000W
10000W
10000W
10000W
10000W
Nominal power at derating
0...P
Nom
0...P
Nom
0...P
Nom
0...P
Nom
0...P
Nom
Accuracy*
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
≤
0.2%
Resolution of display
0.01kW
0.01kW
0.01kW
0.01kW
0.01kW
Efficiency
93%
93%
93%
95.20%
95.20%
Miscellaneous
Ambient temperature
0….50°C
0….50°C
0….50°C
0….50°C
0….50°C
Storage temperature
-20….70°C
-20….70°C
-20….70°C
-20….70°C
-20….70°C
Humidity rel.
< 80%
< 80%
< 80%
< 80%
< 80%
Dimensions (WxHxD) **
19" 3U 595mm
19" 3U 595mm
19" 3U 595mm
19" 3U 595mm
19" 3U 595mm
Weight
33kg
25.5kg
25.5kg
25.5kg
25.5kg
Redundancy
yes
yes
no
yes
no
Isooutput to enclosure
500V DC
500V DC
500V DC
500V DC
900V DC
Isolation -output to enclosure
Isolation input to output
Cooling
Safety
EMC standards
Overvoltage class
Protection class
Pollution degree
Operational altitude
Series operation
max. series connection voltage
Master-Slave
Parallel operation
max. parallel connection voltage
Master-Slave
Analogue programming
Input range
Accuracy
Input impedance
Article number
09230447
09230431
09230433
09230441
09230443
300V DC
1
2
by fans, air inlet on the front, air exhaust on the rear
<2000m
4200V DC
EN 60950
EN 61326, EN 55022 Class B
2
no
600V
1500V
yes, via Share bus
53kOhm
≤
0.2%
0…5V or 0…10V, selectable
* Related to the nominal value, the accuracy defines the maximum allowed deviation between set value and actual value.
Example: a 80V model has min. 0.2% voltage accuracy. This is 160mV. When setting a voltage of 5V and with an allowed maximum deviation of 160mV, the resulting
actual value could be between 4.84V and 5.16V.
** Enclosure dimensions only, not overall dimensions