ELETTROMECCANICA DELTA S.p.A. - Via Trieste 132, 31030 Arcade (TV) ITALY - tel. ++39 0422 874068 - fax ++39 0422 874048
EVRM-NA SAFETY SOLENOID VALVE
100% TESTED
TWO YEARS WARRANTY
The EVRM-NA type valve is a manual reset safety valve that is normally open. A manual operation is
therefore necessary to open the valve and set the mechanism consenting to maintain this state. The
powering by means of line current and/or condenser discharge, induced by the leakage detector,
causes tripping of the mechanism and consequent closing of the gas passage. If energizing of the
sensor persists due to the presence of gas, the valve remains under power and does not allow reset.
When the causes for locking have been eliminated, the valve may be reopened by working it
manually. This type of device, connected with one or more leakage detectors or alarm signals for the
presence of carbon monoxide, is suitable for performing locking operations on the gas line.
INSTALLATION AND ADJUSTMENT
Check correspondence of flow direction with arrow printed on valve body, check correct alignment of
connecting pipes. Valve may be mounted with coil in horizontal or vertical position. Coil may be
oriented 360 degrees in any direction. Install in an area that is protected from rain and water splashes
or drops.
For electrical connection remove cap on the DIN plug and connect power cables to rectifier circuit
clamps.
CLEANING AND MAINTENANCE
Dust and any foreign bodies may be easily removed from the filter or the gas passage zone. After
shutting off upstream gas and electric current, the coil is removed by unscrewing the reset knob and
the knurled fastening cap. Unscrew the 4 screws fixing the counter flange to valve body. During this
operation care should be taken not to cause damage to the seat.
Avoid dissembling or tampering with the reset mechanism.
TECHNICAL CHARACTERISTICS
f/f Connections
: gas threaded from 3/8" to 2" flanged
: flanged PN16 – UNI 2223 from DN65 to DN100
Voltage rating
:
230V-110V AC, 24V-12V AC/DC
Voltage tolerance
: -15% ÷ + 10%
Working temperature
: -15°C ÷ + 60°C
Working pressure
: 500 mbar
Closing time
: < 1 second
Protection class
: IP 54
Cable gland
: PG 9
Pressure inlets
: 1/4" on two sides (except brass model)
This control must be installed in compliance with the laws in force.
Elektrogas reserves the right to update or make technical changes without prior notice.