Parameter description
10
06 Parameter heating circuit
03:04
Building type
Setting range:
1: Light construction (mean value over 6 X3
hours)
2: Medium construction
(mean value over 24 hours)
3: Heavy construction
(mean value over 72 hours)
Factory setting:
2
Function:
This parameter considers the building type by adapting the
calculation of the outside temperature mean value according to
its setting.
03:05
Climate zone
Setting range:
-50°C … 0°C
X3
Factory setting:
-12?
Function:
The climate zone is the coldest outside temperature value to be
expected.
03:06
Automatic exit time
Setting range:
0,5 ... 10 Min
X3
Factory setting:
2 min
Function:
When unit is not operated during the set time, the display
returns to basic display.
03:07
Anti-blocking
protection
Setting range:
0 = OFF
X3
1 = ON
Factory setting:
OFF
Function:
With this function activated, pump is switched on daily for ca. 20
seconds as protection against blocking during extended switch-
off phases (> 24h).
03:09
Code heating
specialist
Setting range:
0 … 999
Factory setting:
0
Function when setting is greater than 0:
Hide parameters marked with X3.
03:10
Total reset
Reset to factory settings
Display
Designation
Description
06:01
Function
Setting range:
0=OFF
1=Unmixed circuit
2=Mixed circuit
Factory setting:
2
Display
Designation
Description