Parameter description
14
08 Parameter Delta-T
06:18
Minimum
temperature limit
Setting range:
5…95°C
X3
Factory setting:
20°C
Function:
This function limits the flow temperature of the heating circuit.
The set temperature will be maintained.
06:19
Maximum
temperature limit
Setting range:
5…95°C
X3
Factory setting:
75°C
Function:
This function limits the flow temperature of the heating circuit.
The set temperature will not be exceeded.
06:20
Heat generator
parallel shift
Setting range:
0…20K
X3
Factory setting:
4K
Function:
The demand value of the heating circuit, plus the shift value, is
transmitted to the heat generator.
06:24
Actuator running
time
Setting range:
0…10 Min
X3
Factory setting:
2 min
Function:
Use this setting to adjust the control characteristic of the mixing
valve to the running time of the actuator in increments of 0.1
minutes (6 seconds).
Display
Designation
Description
08:01
Control mode
Setting range:
0 = Delta T OFF
1 = Delta T ON
Factory setting:
1
Function:
The differential control can be switched on or off via the setting.
08:02
Switch-on difference Setting range: (Switch-off diff 3K) ... 30K
Factory setting:
10K
Function:
If the temperature difference between the sensors of heat
supplier F3 and heat storage tank F1 exceeds the set value, the
pump turns on.
08:03
Switch-off difference Setting range: 2K ... (Switch-on difference - 3K) Factory setting:
5K
Function:
If the temperature difference between the sensors of heat
supplier F3 and heat storage tank F1 drops below the set value,
the pump turns off.
Display
Designation
Description
BA_CETA106_EbV_EN_0450021003_0950-10.book Seite 14 Freitag, 11. Dezember 2009 1:16 13