User Manual
EM303B General Purpose Inverter
139
If auxiliary speed + primary speed > the upper limit frequency, inverter will output as per
the upper limit frequency.
F9-03 ones place =1/2 can be switched to the status of F9-03 tens place =0 through
multi-function terminal.
F9-03 tens place is for speed setting mode when jog control mode is enabled.
F9-03 tens place=0
If jog command is enabled, speed setting value=F0-11 Jog numeric
frequency.
F9-03 tens place=1
If jog command is enabled, speed setting value=F0-11 Jog numeric
fr Primary speed setting.
F9-03 tens place=2
If jog command is enabled, speed setting value=F0-11 Jog numeric
fr auxiliary speed setting (Please pay attention to that the value is positive or
negative).
F9-03 tens place=1/2can be switched to the status of F9-03 hundreds place =0 through
multi-function terminal.
F9-03 hundreds place is for selecting the relation between auxiliary speed and primary
speed.
F9-03 hundreds place=0
Primary speed + auxiliary speed
F9-03 hundreds place=1
Primary speed - auxiliary speed
1.
Please confirm the integrated speed setting mode first, and then confirm the
primary speed setting mode and the setting method in jog control mode.
2.
Primary speed s auxiliary speed setting can be considered as converting
those 2 signals into 0~10V voltage signal, and then take the sum of them as the integrated
speed setting. If the sum>10V, it will be considered as 10V.
3.
Numeric s analog setting can be considered as converting the analog setting into
the corresponding setting frequency, and then add numeric setting frequency. Please note that
if the sum is greater than the upper limit frequency, inverter will output as per the upper limit
frequency.
8.11.4
Special Speed Setting Mode
No.
Function
Range
Unit Default Type
F9-04
Special
Speed
Setting Mode
0: Program Operation
1: Wobbulation Mode
2: Stepping Mode 0
3: Stepping Mode 1
4: Stepping Mode 2
5: Stepping Mode 3
6: Stepping Mode 4
7: Stepping Mode 5
0
〇
F9-04=0 Program Operation
If F0-26 is selected as special speed setting mode, inverter will run in program setting mode.
See 7.8 for program running setting.