User Manual
EM303B General Purpose Inverter
149
8.13.8
Energy Saving Operation
No.
Function
Range
Unit Default Type
FC-10
Energy Saving
Operation Options
0: Energy saving operation disabled
1: Energy saving operation enabled
0
〇
FC-11
Energy Saving
Running
Initial Frequency
10.00
~
600.00/10.0
~
600.0
Hz
20.00
〇
FC-12
Energy Current
Detecting Range
20.00
~
80.00
%
40.00
〇
FC-13
Energy Saving
Delay Start Time
0.01
~
60.00
S
0.50
〇
FC-14
Permitted Energy
Saving Range
60.00
~
100.00
%
80.00
〇
FC-10=1, energy saving operation control is enabled. When inverter runs in idling or on light
load (output current of inverter< the setting value of FC-12), if the output frequency >energy
saving starting frequency (Set by FC-11), inverter will test load current automatically and
make a record of time. If the setting time of FC-13 can meet energy saving needs, the output
voltage shall be dropped to energy saving permitted range (Set by FC-14) to start energy
saving operation. When output frequency< the starting frequency of energy saving or load is
increasing, inverter will withdraw from energy saving operation status. Output voltage will
reset corresponding value.
If output current of inverter > the setting value of FC-12, automatic energy saving is disabled.
See Figure 7-34 for operation process of automatic energy saving.
Output
Frequency
(
Hz
)
Output
Voltage(%)
Starting Frequency of
Energy Saving Operation
FC-11
Energy
Saving
Delay Start
Time
FC-13
Energy Saving
Operation
Time (S)
Energy Saving
Permitted Range
FC-14
See Figure 7-34 Operation Process of Automatic Energy Saving
In V/F control mode, the percentage of output voltage is the energy saving permitted
range.