User Manual
EM303B General Purpose Inverter
96
F2-05
Multi-function Input Terminal
X6-FRS
9
〇
F2-06
Multi-function Input Terminal
X7-RST
10
〇
F2-08
VS Input Function Defining
See FE-04 for setting
of switching analog
function to numeric
function
0
〇
F2-09
IS Input Function Defining
0
〇
F2-10
VF Input Function Defining
0
〇
F2-11
IF Input Function Defining
0
〇
Multi-function input terminals X1
~
X7 are 7 programmable numeric input terminals. The
function of X1~X7 can be defined by the setting value of F2-00
~
F2-06.
For example, set F2-00=1, then the function of terminal X1 is RUN-run. If start/stop
control mode is in terminal control mode, when terminal X1 is on, inverter runs.
Xi=0
No function
This function can be used to block the terminal when its hardware breaks down.
Xi=1
RUN-run
When start/stop control mode is terminal control (F0-04=1), if the function terminal is
on, the inverter will run as per the setting value of F0-05.
Xi=2
F/R Forward/Reverse
When start/stop control mode is in terminal control mode (F0-04=1), if the function
terminal is on, the inverter will forward/reverse as per the setting value of F0-05.
Xi=3
Preset Speed Terminal 1
Xi=4
Preset Speed Terminal 2
Xi=5
Preset Speed Terminal 3
Xi=6
Preset Speed Terminal 4
In preset speed control mode, 4 function input terminals can be defined as the preset
speed terminals. A preset speed set in F3-00
~
F3-14 is selected as the present setting
frequency of inverter by the programming coding of these 4 terminals. See 7.4 for
preset speed options setting.
Xi=7
Acceleration/Deceleration Time Terminal 1
Xi=8
Acceleration/Deceleration Time Terminal 2
F0-09
,
F0-10
,
F3-15
~
F3-20 set acceleration/deceleration time 1
~
4, and select
corresponding
acceleration/deceleration
time
1~4
through
programming
acceleration/deceleration terminals.
See 7.4 for the correlation of acceleration/deceleration time and its terminal.
Xi=9
Coast to stop
Inverter is running, if the function terminal is on, PWM output will be locked
immediately, and then motor coasts to stop.
Xi=10
Inverter fault reset input
Inverter can be reset through fault reset terminal after inverter fault is cleared.
Xi=11
Forward Jog FJOG
Xi=12
Reverse Jog RJOG
Inverter will forward when terminal FJOG is on, reverse when terminal RJOG is on,