User Manual
EM303B General Purpose Inverter
97
and stop when FJOG and RJOG are on simultaneously. See 7.1 for detail of Jog
operation.
Reverse jog is disabled when reverse is prohibited.
Xi=13
UP: Terminal controls numeric frequency, and the stepping frequency rises.
Xi=14
DOWN: Terminal controls numeric frequency, and the stepping frequency drops.
During operation, if it is in stepping mode, the terminals are the hot keys for
stepping frequency. Its speed rate can be set by F9-07.
Xi=15
Clearing the frequency enabled by UP/DOWN
Xi=16
Acceleration/Deceleration prohibited
When acceleration/deceleration prohibition terminal is on, acceleration/ deceleration
command is prohibited, and the output frequency of inverter remains unchanged.
When inverter is in overcurrent protection status, it runs as per the current limiting
mode.
Xi=17
Ramp to stop
Xi=18
3-wire sequence stop control
The function is NC stop button of 3-wire sequence. See F0-05 for details of terminal
start/stop options.
Xi=19
Not used
Xi=20
Switch drive control mode to V/F control mode
No matter what drive control mode F0-02 is in, if the terminal is on, the drive control
mode will be switched to V/F control mode, and its function is equivalent to F0-02=0.
When the terminal is off, it returns the previous control mode automatically.
Xi=21
Switch run command to terminal control
When the terminal is on, no matter what run command mode F0-04 is in, and what
status of the run command input 0 or input 1is, it is always in terminal control mode
which is placed in the highest priority. The terminal control mode is set by F0-05.
Xi=22
Run command input 0
Xi=23
Run command input 1
The run command control modes can be selected through programming the run
command inputs. See Table 7-1 for the correlation between run command control
mode and run command input.
Table 7-1 Correlation between run command control mode and run command inputs
Run Command Input 0
Run Command Input 1
Run Command Control Mode
OFF
OFF
F0-04 Start/Stop Mode
OFF
ON
Keypad
ON
OFF
RS485
ON
ON
External Terminal
Programming mode of run command inputs is prior to F0-04 run command mode selection.
Xi=24
Switch input control mode to speed control mode
When the terminal is on, the present input control mode is switched to the speed
control mode, and its function is equivalent to F0-03=0. After the terminal is off,
inverter returns the previous input control mode automatically.