User manual:
RDO3x3A
34
Par 126
Input Bh2: Operating hours 2 (terminal 4)
K
1:
2:
3:
4:
230VAC
input
0 Counter for operating hours burner 2
1 Signal: Burner malfunction
2
DHW
thermostat
3 Release DHW electrical charge
4 Qmin-limiter for DHW district heating
69 Signal: Burner malfunction without operation stop
70 Block energy function after flow control deviation (Par.10n)
151..194 As in list of parameter 120 (RDO only)
Par 127
Input flow temperature sensor (terminal 29)
0
No
function
20 Input for flue gas temperature sensor
21 Input for flow temperature sensor 2
22 Input for DHW temperature sensor 2 (bottom)
23 Input for flow temperature sensor 1
24 Input for return temperature sensor 1
25 Input for buffer storage temperature sensor 1
26 Input for buffer storage temperature sensor 2 (bottom)
27
Input for return temperature sensor (primary side of HE for DHW charge)
28
Input for solar collector temperature sensor 1
30
Input for DHW temperature sensor 1
Par 128
Input return temperature sensor (terminal 30)
Parameter list as Par.127
Par 129
Output independent time switch channel 9
0
No
output
1 External relay PWM1
(terminal 24; ext. relay)
2 External relay PWM2
(terminal 23; ext. relay)
3
DHW
pump
(terminal
15)
4 Boiler circuit pump
(terminal 8)
5 Mix circuit pump 1
(terminal 9)
6 Mixing valve 1 ON
(terminal 10)
7 Mixing valve 1 OFF
(terminal 11)
8 Mix circuit pump 2
(terminal 44)
9 Mixing valve 2 ON
(terminal 42)
10 Mixing valve 2 OFF
(terminal 41)
11
Burner
1
(terminal
13)
12 Burner 2 ON
(terminal 6)
13 Burner 2 OFF
(terminal 7)
Par 12A
Output 2
nd
source switching point
Parameter list as Par.129
Par 12b
Output error warning
Parameter list as Par.129
Par 12c
Input multi switch 9.1: (R=10kOhm on terminal 27)
Note:
Parameter list as Par.120, only digital functions!
Note:
Set Par.125 to 101.
Par 12d
Input multi switch 9.2: (R=22kOhm on terminal 27)
Note:
Parameter list as Par.120, only digital functions!
Note:
Set Par.125 to 101.
Par 12E
Input multi switch 9.3: (R=47kOhm on terminal 27)
Note:
Parameter list as Par.120, only digital functions!
Note:
Set Par.125 to 101.
Par 12F
Input multi switch 9.4: (R=100kOhm on terminal 27)
Note:
Parameter list as Par.120, only digital functions!
Note:
Set Par.125 to 101.
Par 12L
Output independent time switch heating circuit 7
Parameter list as Par.129
Par 12n
Output independent time switch DHW circuit 4
Parameter list as Par.129