User manual:
RDO3x3A
40
Par 169
Source of outdoor temperature
K
1: 2: 3: 4: 5: 6: 7:
0
No outdoor temperature sensor used (room temperature control)
1 Outdoor temperature sensor 1 (Ba1) used
2
Outdoor temperature sensor 2 (Ba2) used
3
Mean value of outdoor temperature sensors 1 and 2 (Ba1, Ba2) used
4 Outdoor temperature sensor at heating circuit module RZM510 used
5 Outdoor temperature at BCB
6 Outdoor temperature at D-Bus
9 Without heating circuit setpoint
Par 16A
Source of boiler temperature
0 Internal boiler temperature sensor used
1 Boiler temperature sensor at BCB
Par 16b
Source of return temperature
0 Internal return temperature sensor used
1 Return temperature sensor at BCB
Optimization
Par 170
Thermal lag of building
K
1: 2: 3: 4: 5: 6: 7:
0 No lag
(for testing purposes only)
1 Light design
(no or light insulation)
2 Normal design
(medium or good insulation)
3 Heavy design
(very good insulation)
Par 171
Boost heating cut-off
K
1: 2: 3: 4: 5: 6: 7:
0 Economy : Floor heating and radiators (Trsoll -0.75°K)
1 Normal
: Radiator heating only (Trsoll -0.25°K)
Par 172
Optimization of heating circuit switching times
K
1: 2: 3: 4: 5: 6: 7:
Note:
Switching times see Par.173, Par.174
0 OFF:
Begin and end of heating period according heating circuit time switch program
1 ON:
Begin and end of heating period advanced to heating circuit time switch program
2 Ramp function for begin of heating (defined by parameter 173)
Par 173
Maximum time shift for heating start [min]
K
1: 2: 3: 4: 5: 6: 7:
0..180
Heating start earlier than time programmed
Par 174
Maximum time shift for heating end [min]
K
1: 2: 3: 4: 5: 6: 7:
0..120
Heating end earlier than time programmed
Par 175
Optimization of DHW charge switching times
K
1:
2:
3:
4:
0 Release of DHW charge according to the DHW time switch program
1 Release of DHW charge 1 hour prior to the heating start
2 DHW charge continuously released (no programming possible)
Configuration of special operation modes
Par 180
Automatic short herm heating limit
K
1: 2: 3: 4: 5: 6: 7:
Note:
- Mode switch must be set to any heating operation.
- Limit is based on calculated flow temperature setpoint
0
OFF
1 ON: Automatic heating limit activated
2 As 1, ambient frost protection activated by parameter 187