User manual:
RDO3x3A
46
Outputs that are allocated to heat generator:
Burner
2-step
Burner
modulating
BrA with
RZM530A
District
heating
K
Par. Terminal:
Key: - / +
- / +
- / +
- / +
+70 14
Burner 1
off / on
off / on
+71
6
Burner 2 on/OPEN
¦ off / on ¦
¦ off / on ¦
¦ off / on ¦
7
Burner 2 off/CLOSE
¦ on / off ¦
+72
7
Burner 2 off/CLOSE
¦ on / off ¦
¦ off / on ¦
+73
8
Boiler circuit pump KK
off / on
off / on
off / on
+75
9
Mix-circuit pump MK1
off / on
off / on
+76 10
Mixing valve 1 OPEN
¦ off / on ¦
¦ off / on ¦
+77 11
Mixing valve 1 CLOSE
¦ on / off ¦
¦ on / off ¦
+78 24
PWM1
BrA=Gas module for burner
Outputs that are allocated to DHW:
WWel: Electrical charging released
WWZ: Circulation pump released
K
Par.116=
1,2,3,11,12
13,14,15,17
16
Par. Terminal:
Key:
- / +
- / +
- / +
+80 (10)
DHW mixer 1 OPEN
¦ off / on ¦
¦ off / on ¦
+81 (11)
DHW mixer 1 CLOSE
¦ off / on ¦
¦ off / on ¦
+82 6
DHW mixer 2 OPEN
Wwel
WWel
¦ off / on ¦
+83 7
DHW mixer 2 CLOSE
WWZ
WWZ
¦ off / on ¦
+84 15
DHW pump
off / on
(off / on)
WWZ
+85 10
DHW mixer pump
(off / on)
off / on
off / on
Auxiliary inputs
They're indicated by the weekday cursors as long as
they're active (connected to GND).
Weekday:
1 2 3 4 5 6 7
=active
Terminal:
35 34 33 32 31 3 4
Designation: Ext.1
Ext.2
Bag
Bww
Bres
Bh1
Bh2
Function
"digital": Ext.1 Ext.2 Ext.3 WW-Th Ext.5 Bh1
Bh2
+52 digital inputs:
Ext.2.1
Ext.2.2 Ext.2.3 Ext.2.4
+59 digital inputs:
Ext.9.1
Ext.9.2 Ext.9.3 Ext.9.4
RZM515A: Ext.1
Ext.2
WW-Th
WWel
Choose application:
+90 x : Select application register
+90 x : Select number of desired application
A list of all applications and the detailed information are available.
Application "0" to reset all counters!
+90 x : Press key
for 5 seconds
All controllers are delivered with Par.+90=1!
Resetting controller to application main parameters:
+90 x : Select application register, check number of desired application
+90 x : Press key
for 5 seconds, setup controller with application
parameters
Controller type:
+98 383 : Display controller type (353A or 383A)