SINUS-K
PROGRAMMING
MANUAL
111/
226
C83 DCB time 5/9
P
C83
R
0.1÷50s
D
0.5s
at Start =*.**s
F
Determines DC braking time before the acceleration ramp.
C84 DCB Freq 6/9
P
C84
R
0÷10 Hz
D
1 Hz
at STOP =*.** Hz
F
Determines the output frequency for DC braking at stop and affects the formula
expressing DC braking time when the command is sent via terminal board (see
section 3.9.3 “ DC BRAKING COMMAND SENT VIA TERMINAL BOARD “).
C85 DCB Curr. 7/9
P
C85
R
1÷400%
Important: the maximum programmable value is equal to (Imax/Imot)*100 (see
Table 6.4)
D
100%
Idcb =***%
F
Determines DC braking intensity expressed as a percentage of the motor rated
current.
C86 DCB Hold. 8/9
P
C86
R
NO, YES
D
NO
[NO] YES
F
After stopping the equipment through DC current braking, it determines a
continuous DC injection to maintain a braking torque over the motor shaft and to
avoid condensation inside the motor.
C87 DCB Hold. 9/9
P
C87
R
1%÷100%
D
10%
Current ***%
F
Determines the intensity of the permanently injected direct current expressed as a
percentage of the motor rated current.