SINUS-K
PROGRAMMING
MANUAL
53/
226
Press MENU to quit the submenu.
Press
↓
(Dn) and
↑
(Up) to decrease or increase the main reference if (FR) is displayed; press
↓
(Dn) and
↑
(Up) to
decrease or increase PID regulator reference if (RG) is displayed.
Press PROG (
←
) or SAVE (
→
)
to display a different variable in the first line and the quantity managed with
↓
and
↑
.
At first power on, the main reference is set to zero. Then, the reference stored at power off is displayed if parameter
P24 (UD MEM) is set to [YES]. Otherwise, i.e. if P24 = [NO], the main reference is always set to 0 when the inverter is
turned on.
2)
Start Operation = KPD
Ref Operation = Term
PID Ref = KPD
The START command (terminal 7) is disabled in the terminal board.
Press MENU to quit the submenu.
Press PROG (
←
) or SAVE (
→
)
to display a different variable in the first line.
Press
↓
(Dn) and
↑
(Up) to decrease or increase PID regulator reference if (RG) is displayed.
3)
Start Operation = Term
Ref Operation = KPD
PID Ref = KPD
Inputs for the frequency main reference are disabled in the terminal board.
Press MENU to quit the submenu.
Press PROG (
←
) or SAVE (
→
)
to display a different variable in the first line.
Press
↓
(Dn) and
↑
(Up) to decrease or increase the main reference if (FR) is displayed; press
↓
(Dn) and
↑
(Up) to
decrease or increase PID regulator reference if (RG) is displayed.
If a multifrequency/multispeed command is sent, this will become the current reference.
At first power on, the main reference is set to zero. Then the reference stored at power off is displayed if parameter P24
(UD MEM) is set to [YES]. Otherwise, i.e. if P24 = [NO], the main reference is always set to 0 when the inverter is
turned on.
PROG SAVE
Fout = *** Hz
←
→
PROG SAVE
Fout = *** Hz
←
Dn (FR) Up
→