SINUS PENTA
REGENERATIVE
APPLICATION
103/
140
0
1
2
3
4
P570 Undervoltage Alarm Enable
P570
Range
0
÷
0007h
0
÷
0007
Default
0007h
Bit 0
→
1 Enable R phase alarm
Bit 1
→
1 Enable S phase alarm
Bit 2
→
1 Enable T phase alarm
Level
ENGINEERING
Address
690
Function
Bit-controlled parameter: bits 0 to 2 allow enabling (Bit = 1) or disabling
(Bit = 0) the undervoltage alarms of the three mains phases (R, S, T).
P571 Min. Voltage Alarm Enable
P571
Range
0
÷
0007h
0
÷
0007
Default
0007h
Bit 0
→
1 Enable R phase alarm
Bit 1
→
1 Enable S phase alarm
Bit 2
→
1 Enable T phase alarm
Level
ENGINEERING
Address
691
Function
Bit-controlled parameter: bits 0 to 2 allow enabling (Bit = 1) or disabling
(Bit = 0) the RMS min. voltage alarm of the three mains phases (R, S, T).
P572 Max. Voltage Alarm Enable
P572
Range
0
÷
0007h
0
÷
0007
Default
0007h
Bit 0
→
1 Enable R phase alarm
Bit 1
→
1 Enable S phase alarm
Bit 2
→
1 Enable T phase alarm
Level
ENGINEERING
Address
692
Function
Bit-controlled parameter: bits 0 to 2 allow enabling (Bit = 1) or disabling
(Bit = 0) the RMS max. voltage alarm of the three mains phases (R, S, T).
P573 RMS Alarm enable
P573
Range
0
÷
0007h
0
÷
0007
Default
0007h
Bit 0
→
1 Enable R phase alarm
Bit 1
→
1 Enable S phase alarm
Bit 2
→
1 Enable T phase alarm
Level
ENGINEERING
Address
693
Function
Bit-controlled parameter: bits 0 to 2 allow enabling (Bit = 1) or disabling
(Bit = 0) the RMS voltage alarms of the three mains phases (R, S, T).