RIGENERATIVE
SINUS PENTA
APPLICATION
106/
140
0
1
2
3
4
0
1
2
3
4
3.8.
DIGITAL OUTPUTS MENU
3.8.1.
O
VERVIEW
Digital outputs MDO1 and MDO2, Push-Pull and Open Collector outputs respectively, can be set up with the
parameters contained in the Digital Outputs menu.
MDO3 cannot be set up because it is assigned to the closure of the pre-charge contactor.
MDO4 is assigned to the motor drive activation; its activation logic can be programmed through C503.
3.8.2.
L
IST OF
P
ROGRAMMABLE
P
ARAMETERS
P580
AND
P581
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT
VALUES
P580
MDO1 Digital Output Function
BASIC
700
1: Run OK
P581
MDO2 Digital Output Function
BASIC
701
2: Mains
Fault
Table 12: List of parameters P580 and P581.
P580, P581 MDO1, MDO2 Digital Output Function
P580, P581
Range
0
÷
10
0: Synchronization OK
1: Run OK
2: Mains Fault
3: Drive OK
4: Drive in Alarm
5: W40 Fan Fault
6: Precharge OK
7: Command 1 from Fieldbus
8: Command 2 from Fieldbus
9: Command 3 from Fieldbus
10: Command 4 from Fieldbus
Default
1 (P580)
2 (P581)
1: Run OK (P580)
2: Mains Fault (P581)
Level
BASIC
Address
700 701
Function
These parameters set the functions implemented by digital outputs MDO1
and MDO2.
See
Table 13 for more details.