The status of the drive digital outputs in the word is as follows:
bit [15..8]
bit [7..0]
Digital outputs in option boards
Drive digital outputs
Bitmap:
0
→
MDO1
1
→
MDO2
2
→
MDO3
(Prech)
3
→
MDO4
(EnSlv)
6
→
Status of internal pre-charge contactor
8
→
XMDO1
9
→
XMDO2
10
→
XMDO3
11
→
XMDO4
12
→
XMDO5
13
→
XMDO6
Note G)
The full-scale value of
±
16380 is a nominal value and corresponds to an input range of
±
10V. This value can be automatically changed
by the drive due to the tolerance compensation of the input stages.
ALARM A070 COMMUNICATIONS FAILURE
Alarm A070 trips if the Sinus Penta has not received any legal message sent via FIELDBUS for the timeout set
in parameter R016 (please refer to the Sinus Penta’s Programming Instructions manual). To disable alarm
A070, set R016 = 0.
A legal message is sent when the master writes the digital input word (M035) with bit 15=1.
Important: This activates only when the drive receives the first message with bit 15=1.
NOTE
Once changed and saved, R016 has no effect until the drive is next
powered on, or until the control board is reset by holding down the RESET
key for more than 5 secs.