SINUS PENTA
REGENERATIVE
APPLICATION
123/
140
0
1
2
3
4
C502 Mains Fault Enable
C502
Range
0
÷
1
0: No
1: Yes
Default
1
1: Yes
Level
ENGINEERING
Address
1002
Function
This parameter sets the drive operation when a power failure occurs.
If C502 = [0: No], when the mains is out of range if compared to the
thresholds set in the Mains Monitor menu, the drive is disabled for some
time but is not locked in an emergency; otherwise, if C502 = [1: Yes], the
drive locks.
C503 MDO4 Digital Output Function
C503
Range
1
÷
2
0: REGEN ENABLED
1: REGEN RUN or RESET
2: REGEN RUN
Default
2
2: REGEN RUN
Level
ADVANCED
Address
1389
Function
This parameter sets which function is implemented by MDO4 digital
output. See Table 17 for details.