RIGENERATIVE
SINUS PENTA
APPLICATION
132/
140
0
1
2
3
4
0
1
2
3
4
3.17.
EXPANSION BOARD CONFIGURATION MENU
3.17.1.
O
VERVIEW
NOTE
Parameters in this menu are Rxxx parameters.
Once saved, they have no effect until the drive is next powered on, or until the
control board is reset by holding down the RESET key for more than 5 secs.
3.17.2.
L
IST OF
P
ROGRAMMABLE
P
ARAMETERS
R021
TO
R023
Parameter
FUNCTION
User Level
MODBUS
Address
DEFAULT VALUES
R021
Data Logger Setting
ENGINEERING 551 1:
Disable
R023
I/O Board Setting
ENGINEERING 553
0:
None
Table 25: List of parameters R021 to R023.
R021 Data Logger Setting
R021
Range
1
÷
2
1: Disable
2: Enable
Default
1
1: Disable
Level
ENGINEERING
Address
551
Function
This parameter enables or disables Data Logger initialization (if the
Data Logger board is fitted).
R023 I/O Board Setting
R023
Range
0
÷
6
0: None
1: XMDO
2: XMDO + Pout
3: XMDO + PT100
4: XMDO + Pout + PT100
5: XMDO + ADE
6: XMDO + ADE + Pout
Default
0
0: None
Level
ENGINEERING
Address
553
Function
Based on the settings in the respective parameters, this parameter
enables controlling the following items:
XMDO: Digital OUTPUTS (see the AUXILIARY DIGITAL OUTPUTS
MENU);
Pout: DC measures (see the SETTING DC MEASURES MENU);
PT100: Up to 4 PT100 probes (see the SETTING MEASURES FROM
PT100);
ADE: Energy measures through ADE7758 (see the ADE REGISTERS
MENU).
NOTE
ES847 is required to control DC measures, PT100 probes and energy delivery
via ADE7758.
Both ES847 and ES870 can be used for controlling XMDO digital outputs.