SINUS PENTA
REGENERATIVE
APPLICATION
117/
140
0
1
2
3
4
3.11.5.
F
ROM THE
S
INUS
P
ENTA TO THE
M
ASTER
1) Position
2) ID
3) Description
4) Range
5) Unit of
Measure
6) Ratio
1
Alarms
–
Note D)
–
2
M501 DC-bus
Voltage
0
÷
65000
V 1/10
3
M503 Drive
Current
0
÷
65000
A 1/10
4
(default
M505)
Measure 3
configurable with P330 *
see Programmed measure
5
(default
M502)
Measure 4
configurable with P331 *
see Programmed measure
6 DIN
Digital
Inputs
– Note E) –
7 DOU Digital
Outputs
– Note F)
–
8
REF
REF Analog Input
– 16380
÷
+ 16380
Note G)
–
9
AIN1
AIN1 Analog Input
– 16380
÷
+ 16380
Note G)
–
10
AIN2
AIN2 Analog Input
– 16380
÷
+ 16380
Note G)
–
* The exchanged parameters can be customized by properly setting P330 and P331 (see the FIELDBUS
MENU). As per the unit of measure and the scaling range, please refer to the “Range” line in the table relating
to the selected measure (Measures section). Example:
M505 Delivered Active Power
M505
Range
±
32000
±
3200.0 kW
Address
1655
Function
Active power exchanged with the mains.
The positive sign stands for the power delivered to the regenerative drive
(power flow from AC mains to regenerative drive); otherwise, the negative
sign is displayed.
As shown in the “Range” line, the measure of the active power is given with one decimal figure, so the scaling
ratio is 1/10.