3.13.
CONTROL METHOD MENU
3.13.1.
O
VERVIEW
The Control Method menu allows selecting one of the three control sources below:
0: Disable
1: Terminals
2: Serial Link
3: Fieldbus
For more details, please refer to the Control Method section in the Sinus Penta’s Programming Instructions
manual (parameters C140 to C142).
If multiple control sources are selected, the logic status of the ENABLE command and the digital inputs
programmed as external trips (if any) depend on the control terminals resulting from the AND of all the active
control sources.
NOTE
For the activation of the ENABLE command, always close the MDI2 input in the
terminal board, whatever control source is selected.
NOTE
Whatever control source is selected, the status of MDI4 (Pre-charge Return) and MDI5
(Filter Capacitor Protection) is detected in the local control terminals of the drive.
The logic status of any other programmed digital input is considered by executing the OR between the selected
control sources.