User Manual HPS/P/20kVA 6200591_01_ 

10 

 

1.

 

INTRODUCTION 

 
HPS is a power source that supplies a sinusoidal and stable voltage. Its output voltage is adjustable 
in frequency and amplitude. 
 

1.1.

 

MAIN FEATURES 

 

1.1.1.

 

Output Voltage 

 
The  output  voltage  is  guaranteed  perfectly  sinusoidal,  with  a  distortion  of  less  than  0.6% 
regardless of the load. The value of output voltage is kept perfectly stable within 0.1% with linear 
load and a full load. 
The load that HPS is able to drive can vary from a pure capacity to a pure inductance. 
The output voltage is adjustable with continuity from zero to full scale.  
Furthermore,  HPS  is  capable  to  keep  the  voltage  stable with  time  variable  loads,  as  for example 
the  pulsating  loads.  In  fact  HPS  recovers  the  distortion  of  the  waveform  within  0.1%  and  the 
amplitude of the voltage within 0.6% in less than half period. 
HPS can in fact provide the nominal power at various full scales and this allows the HPS to adapt 
himself to the disparate needs of the user, without having heavy limitations on the output current. 
The HPS has only a three phase output, but It is able to supply a single phase load, in this case the 
maximum power is 1/3 respect to the nominal power  
Furthermore  HPS  is  capable  to  keep  the  voltage  stable  also  with  time  variable  loads,  as  for 
example the pulsating loads. In fact HPS recovers the distortion of the waveform within 0.6 % with 
linear load and the amplitude of the voltage within 0.1% in less than half period. 
Furthermore,  HPS  can  bear  a  short  circuit  for  an  indefinite  time  without  suffering  any 
consequence. 
 

1.1.2.

 

Output frequency 

 
HPS allows the regulation of the output frequency from 50 to 80Hz at maximum voltage. 
This  output  frequency  can  be  regulated  with  continuity  within  the  above  mentioned  range  of 
frequencies and it has a stability of 0.01% with respect to the set frequency. 
HPS  also  allows  to  synchronize  the  output  frequency  with  the  frequency  of  the  supply  line;  this 
synchronization is obtained both in frequency with line. 
This  allows  a  completely  synchronous  output, with  a  zero  phase  error  regard  to the  supply  line, 
but with a completely insulated output and with a far superior voltage stability. 
 

1.1.3.

 

User interface 

 
HPS  is  intended  to  have  an  user  friendly  interface.  It  is  also  featured  the  possibility  of  an  host 
computer  control,  thus  allowing  to  perform  tests  automatically.  HPS  allows  various  usage 
selections:  working  range,  wires  drop  compensation,  working  frequency,  syncronization  of  the 
output frequency with the power line. Furthermore, HPS gives the user clear information on the 
status of the output.  It  is  monitored both the  set  voltage  and  the  set frequency and the  output 
voltage is read with a precision of 0.3%. The user is also warned in case of over current obtainable 
by the HPS, or in case of high loss in the wires, that should not exceed 10% of the set  voltage. 

Summary of Contents for 99116963

Page 1: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 1 HPS P 200K USER MANUAL Clicca qui per vedere la versione in Italiano ...

Page 2: ...ered in this manual Model Code HPS P 200kVA 99116963 This manual is written from HPS P firmware version TPSX 09_ Please check the latest manual version at www elettrotestspa it To consult older manual versions please contact our support at service elettrotestspa it ...

Page 3: ...Description Link QR code User Manual Latest manual version Manual Brochure Brochure for all the TPS HPS CPS models Brochure TPS Parameters Describes all the machine modifiable parameters and the start up sequence TPS Parameters TPS protocol Elettrotest Describes how the Elettrotest remote communication protocol works Elettrotest Protocol TPS protocol SCPI Describes how the SCPI remote communicatio...

Page 4: ... 02 22 User Manual HPS P 20kVA 6200591_01_ 4 Documents Description Link QR code PS Interface Software for remote use PS_interface Driver LabView Manual and LabView Drivers for PS interface Driver LabView ...

Page 5: ...the system must be suitable for the rated voltage and current of HPS model paragraph 1 2 The electrical components which by construction cannot support external influences of the generator in all its range can only be used on condition that adequate additional protection has been provided with automatic disconnection protection Notes This manual lists precautions and information about operating pr...

Page 6: ...his is the time necessary in order for the capacitors inside the device to discharge The non observance of this discharge time can lead to electric shocks even fatal ones Avoid heavy shocks to the equipment especially during transport or exposure to extreme weather conditions Any damage to the product due to transportation incorrect installation or improper use is not covered by the guarantee supp...

Page 7: ...n systems defined by local legislation must be used In addition the equipment can be returned to the manufacturer at the end of its working life when buying new equipment the equipment may contain hazardous substances the improper use or incorrect disposal of such may have negative effects on human health and on the environment the symbol crossed out wheeled bin shown on the product or on the pack...

Page 8: ... MODE 17 2 8 ALARMS 17 2 8 1 SUPPLY ALARMS 17 2 8 2 SYSTEM ALARMS 18 2 8 3 CURRENT ALARM 18 2 8 4 VOLTAGE ALARM 18 2 9 PARALLEL OPTION 18 2 9 1 TURN ON 18 2 9 2 CHANGE CONFIGURATION MASTER AND SLAVE 19 2 9 3 TURN OFF 19 3 INSTALLATION 20 3 1 GENERAL NOTES 20 3 1 1 POWER CABLING 20 3 1 2 SIGNAL CABLING 21 3 2 FUSES 22 3 3 RCD PROTECTION 22 3 4 MAGNETO THERMAL PROTECTION 22 3 5 WIRING DIAGRAM 22 3 5...

Page 9: ...IMUM OUTPUT VOLTAGE VS FREQUENCY 32 5 3 2 INRUSH CURRENT VS TIME 32 5 4 Internal fuses 33 5 4 1 99116963 HPS200K 33 5 5 Accessory 33 5 5 1 99116963 HPS200K 33 6 SERVICE AND MAINTENANCE 34 6 1 MAINTENANCE CLEANING 34 6 1 1 Scheduled maintenance 34 6 2 ALARMS DIAGNOSIS AND REPAIRS 34 6 3 BASIC TROUBLESHOOTING 35 6 3 1 Overvoltage Undervoltage alarms 35 6 3 2 Overtemperature 35 6 3 3 Inverter Alarm 3...

Page 10: ...t HPS recovers the distortion of the waveform within 0 6 with linear load and the amplitude of the voltage within 0 1 in less than half period Furthermore HPS can bear a short circuit for an indefinite time without suffering any consequence 1 1 2 Output frequency HPS allows the regulation of the output frequency from 50 to 80Hz at maximum voltage This output frequency can be regulated with continu...

Page 11: ...f the normal operating limits they are not valid during the limitation of the output current 1 With linear load f s stands for Full Scale s v stands for Set Value 1 1 5 General specifications The voltage is referred phase to neutral with neutral connected to the earth PARAMETER VALUE Output frequency range 1 2 50Hz 80Hz Range of synchronization 45Hz 65Hz Phase resolution 0 088 12 bit su 360 Freque...

Page 12: ... all specifications are for L N Phase angle specifications are valid under balanced load conditions only MODELS NOMINAL OUTPUT POWER SUPPLY VOLTAGE WEIGHT INPUT CURRENT INPUT POWER DIMENSIONS A L P mm HPS P 200K 200KVA 400Vac 10 3PH 1800 Kg 500A max 230KW 1800 1600 1000 99116963 HPS 200K 120K360S Configuration INRUSH FOR 3 SEC COUNTINOUS COUNTINOUS LOAD L N L L Range 300 519 3 PHASE 433 4 A 164 2 ...

Page 13: ...ecked see at the voice alarms When the test ends HPS is set to 0 Volt in the range 300 Volt 50 Hertz and regulation on the output terminals 2 wires After the appearing of these indications HPS is ready to work 2 2 PARAMETERS PROGRAMMING MODE HPS T allows you to change various generator start parameters through the programming mode The programming mode allows you to configure a starting profile of ...

Page 14: ... up as soon as the connection takes place the display stops to flash and the led PROGRAM shuts off In case of error you can push the button CLEAR which causes the exit from the programming routine The maximum voltage is equal to the set of the range Moreover if the set of the voltage is not coherent with the set off range for example the setting of a voltage exceeding the range the datum is not ac...

Page 15: ...zes zero voltage 0 0 since that moment HPS is ready to receive the setting on the new range 2 5 VOLTAGE VISUALIZZATION The display concerning the output voltage can visualize four values the set voltage or the output voltage for each phase At turn on the display visualizes the set voltage and this is indicated by the led on the button SET in the DISPLAY VOLT section of the panel In order to visual...

Page 16: ...inner frequency reference with a precision of 0 01 the second one is the line of loading frequency At turn on HPS is connected to the inner reference and this state is signalled by the led corresponding to the button INT at the voice FREQ REF To connect the output frequency to the network frequency push the button LINE in this case the output frequency is brought at 50 Hertz this is indicated by t...

Page 17: ... After exceeding this limit HPS doesn t guarantee that the value of the output voltage is equal to the set up voltage and is visualized a signal of error see at voltage alarms 2 7 2 TYPE OF OUTPUT There is only the three phase output The output power is variable to type of the load for resistive load the power is nominal power for inductor load is greater than the nominal power for capacitor load ...

Page 18: ...e output sinusoidal wave is no more guaranteed and so it will show an harmonic distortion Not linear loads with an overload less than the nominal one but with a very high crest factor current allow the current defence Notice that if someone is working by limitation current HPS keeps the effective value of the output voltage equal to the set off value until the led concerning the voltage alarm swit...

Page 19: ... to change the configuration with the contacts 1 7 and 1 8 4 Set the configuration Master and Slave with the commands 1 1 and 1 2 5 Turn on the machine with the commands 1 7 and 1 8 6 Set the mode of the machines remote range sensing You have to set only the master machine 7 Enable the lines 8 The system is ready 2 9 3 TURN OFF Down the steps you have to do to turn off the system the system 1 Set ...

Page 20: ...nel Remove the internal short circuit OUTPUT NEUTRAL PE this short circuits must be made externally on the star of the output neutral see schematics The signal part and the power part have not to cabled together The master slave commands are all 230V you have to use shielded cable if you cable together with signal one for example the RS232 connections INGRESSO INPUT 1 2 3 4 L1 L2 L3 PE AUX MASTER ...

Page 21: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 21 3 1 2 SIGNAL CABLING ...

Page 22: ...s recommended to use B type RCD with a earth leakage current of 100 mA according to the nominal input characteristic see section 5 1 The machine can absorb more than 100mA at high frequency be secure the RCD has the filter for high frequency 3 4 MAGNETO THERMAL PROTECTION The Magneto thermal circuit breaker protect the input line from short circuits Generally depends on the load and on the connect...

Page 23: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 23 3 5 2 Wiring single three phase diagram of 2 wire configuration ...

Page 24: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 24 3 5 3 Wiring single three phase diagram of 4 wire configuration ...

Page 25: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 25 3 5 4 Wiring diagram three phase of 2 wire configuration ...

Page 26: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 26 3 5 5 Wiring diagram three phase of 4 wire configuration ...

Page 27: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 27 3 5 6 Wiring diagram three phase of 2 wire configuration MASTER SLAVE ...

Page 28: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 28 3 5 7 Wiring diagram three phase of 4 wire configuration MASTER SLAVE ...

Page 29: ...arameters for serial connection BAUD RATE 1200 in standard version DATA BITS 8 STOP BITS 1 4 1 2 Serial cable Use a serial cable according to the standard defined in the figure below 4 2 EXISTENCE TABLE Hereunder is shown the table of existence for the protocols and the hardware MODELS Communication ports Protocols RS232 RS485 LAN Elettrotest Elettrotest RPS SCPI Modbus CPS M X X X X X CPS T X X X...

Page 30: ...ltage RMS 300V 150V Maximum output POWER 200KVA Maximum output inrush current 3 sec 360KVA Output frequency range 50Hz 80Hz 2 3 Dimensions 1800 1600 1000 Weight 1800 kg Protections OVP UVP OTP OCP Operating temperature 0 35 C Storage temperature 20 70 C RS232 Yes RS485 Option LAN Option Safety certification EN 61010 1 EMC certification EN 61000 6 2 4 EN 61000 6 4 5 1 At maximum power 2 Under 50Hz ...

Page 31: ... 02 22 User Manual HPS P 20kVA 6200591_01_ 31 4 4 3 3 3 3 3 3 All measure are on mm 1 On Off Switch 2 Fans 3 Grills 4 Rear panel for connection 5 2 MECHANICAL DRAWINGS 5 2 1 HPS T 200K 1 2 2 2 3 3 3 2 2 2 ...

Page 32: ... User Manual HPS P 20kVA 6200591_01_ 32 5 3 DIAGRAM 5 3 1 MAXIMUM OUTPUT VOLTAGE VS FREQUENCY 5 3 2 INRUSH CURRENT VS TIME 0 00 0 50 1 00 1 50 2 00 2 50 3 00 3 50 0 0 10 0 20 0 30 0 40 0 50 0 60 0 Time sec I Io ...

Page 33: ...00V F9 F10 Auxiliary line 230V 5x20 5 HT 250V F11 F12 Relay board 5x20 2 5 HT 250V F13 F14 Control board 5x20 2 5 HT 250V F15 F16 AUX INVERTER L1 5x20 2 5 HT 250V F17 F18 AUX INVERTER L2 5x20 2 5 HT 250V F19 F20 AUX INVERTER L3 5x20 2 5 HT 250V F21 F22 Not Used 5x20 2 5 HT 250V 5 5 Accessory 5 5 1 99116963 HPS200K Description Pcs 1 FUSE NH3 630A GG 690V 2 2 FUSE 10x38 4A AM 500V 2 3 FUSE 5x20 5A H...

Page 34: ...S Pworking hours 20000 Hours to change the fans 40000 Hours to change the capacitors From 7 to 10 Years for general maintenance You can check the HPS P working hours both on the display and via remote Please note that it is necessary to return the machine to ELETTROTEST S P A for the scheduled maintenance 6 2 ALARMS DIAGNOSIS AND REPAIRS If one or more alarms are shown the user must not try to rep...

Page 35: ...ice 6 3 2 Overtemperature Cause Solution Wrong input connections Open the input connections and check the input voltage that needs to be 230V 10 for 1Phase machines and 400V 10 for 3Phases machines Broken fuse Check all the fuses Power from EUT to TPS TPS don t accept power from the EUT Cause Solution Fans coverage Check that all the ventilation parts need to be not cover and air filters must be c...

Page 36: ...on Low voltage setted If a very low voltage is set DV OUT led is generally on Wrong 2 4 wires configuration Check with the schematics the voltage inside the machine The thermal switch is closed when it s not in alarm Output current limitation Check the output voltage and current Calibration The machine is out of calibration Please contact the service Cause Solution Overload Chek the output voltage...

Page 37: ...e apparatus in case of periodic verification always 8 REVISION INDEX Elettrotest Spa is committed to a program of continuous improvement of products and information to the customer Therefore the company reserves the right to make changes to the documentation and specifications without notice and assumes no responsibility for any incorrect information Rel Date Descriptions 01_ 03 02 22 Added Quick ...

Page 38: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 1 HPS P 200K MANUALE UTENTE Click here to see the English version ...

Page 39: ...e Modello Codice HPS P 200kVA 99116963 Questo manuale è scritto per le versioni firmware dalla TPSX 09_ Controlla sempre l ultima versione del manuale al sito www elettrotestspa it Per consultare manuali di versioni precedenti contatta il supporto Elettrotest service elettrotestspa it ...

Page 40: ...hai bisogno Documents Description Link QR code User Manual Latest manual version Manual Brochure Brochure for all the TPS HPS CPS models Brochure TPS Parameters Describes all the machine modifiable parameters and the start up sequence TPS Parameters TPS protocol Elettrotest Describes how the Elettrotest remote communication protocol works Elettrotest Protocol TPS protocol SCPI Describes how the SC...

Page 41: ...Manual HPS P 20kVA 6200591_01_ 4 Documenti Descrizione Link QR code PS Interface Programma per l utilizzo della macchina in remoto PS_interface Driver LabView Manuale e Driver LabView per PS interface Driver LabView ...

Page 42: ...ici dell impianto devono essere idonei alla tensione e alla corrente nominali del tuo modello HPS I componenti elettrici che per costruzione non possono sopportare influssi esterni dal generatore possono essere utilizzati solo a condizione che sia stata prevista un adeguata protezione aggiuntiva con disinserimento automatico Note Questo manuale elenca le precauzioni e le informazioni sulla procedu...

Page 43: ...da almeno 5 minuti Questo è il tempo necessario affinché si scarichino i condensatori presenti all interno Il non rispetto di questo tempo può portare a shock elettrici anche mortali Evitare di sottoporre il prodotto a forti urti specialmente durante il trasporto o a condizioni climatiche estreme Il danneggiamento del prodotto dovuto al trasporto installazione o utilizzo improprio non rientra nell...

Page 44: ...izzati i sistemi di raccolta pubblici o privati previsti dalle leggi locali È inoltre possibile riconsegnare al produttore l apparecchiatura a fine vita in caso di acquisto di una nuova Questa apparecchiatura può contenere sostanze pericolose un uso improprio o uno smaltimento non corretto potrebbe avere effetti negativi sulla salute umana e sull ambiente Il simbolo contenitore di spazzatura su ru...

Page 45: ...O SPUNTO 16 2 8 ALLARMI 17 2 8 1 ALLARMI DI ALIMENTAZIONE 17 2 8 2 ALLARMI DI SISTEMA 17 2 8 3 ALLARME DI CORRENTE 17 2 8 4 ALLARME DI TENSIONE 18 2 9 OPZIONE PARALLELO 18 2 9 1 ACCENSIONE 18 2 9 2 CAMBIO CONFIGURAZIONE MASTER SLAVE 18 2 9 3 SPEGNIMENTO SISTEMA 18 3 INSTALLAZIONE 19 3 1 NOTE GENERALI 19 3 1 1 Ispezione prodotto 19 3 1 2 CABLAGGIO DI POTENZA 20 3 1 3 CABLAGGIO DEI SEGNALI 21 3 2 FU...

Page 46: ...S P 200K 31 5 3 DIAGRAMMI 32 5 3 1 TENSIONE MASSIMA IN FUNZIONE DELLA FREQUENZA 32 5 3 2 CORRENTE DI SPUNTO E TEMPO 32 5 4 Fusibili interni 33 5 4 1 99116963 HPS200K 33 5 5 Accessori 33 5 5 1 99116963 HPS200K 33 6 MANUTENZIONE E SERVICE 34 6 1 MANUTENZIONE E PULIZIA 34 6 1 1 Manutenzione programmata 34 6 2 RIPARAZIONE E DIAGNOSI ALLARMI 34 6 3 RISOLUZIONE PROBLEMI BASE 35 6 3 1 Allarmi di sovraten...

Page 47: ...sere utilizzato in monofase utilizzando una sola fase in questo caso la potenza massima e 1 3 rispetto la potenza nominale L HPS e inoltre in grado di mantenere la tensione stabile anche con carichi variabili nel tempo come ad esempio carichi pulsanti l HPS recupera infatti la distorsione della forma d onda entro lo 0 6 con carico lineare e l ampiezza della tensione entro lo 0 1 in meno di mezzo p...

Page 48: ...lle diverse applicazioni dove sia richiesta una va riazione continua delle due grandezze di regolazione attorno a un dato valore 1 1 4 Prestazioni generali Tutte le caratteristiche seguenti sono valide entro il regime di normale funzionamento 1 Con carichi lineari f s Fondo Scala s v Valore impostato 1 1 5 Specifiche generali PARAMETRO VALORE Range frequenza di uscita 1 2 50Hz 80Hz Range di sincro...

Page 49: ...ento è valido solo per carico bilanciato 2 NOTE DI UTILIZZAZIONE 2 1 ACCENSIONE All atto dell accensione tramite l interruttore presente sul frontale della macchina l HPS compie vari cicli di test indicati dal progredire dei numeri da 0 a 9 sui display Nel caso di malfunzionamento il test si ferma e la macchina indica sul frontale il tipo di allarme che si e verificato vedere la voce alarmi Quando...

Page 50: ...n una freccia verso l alto e una verso il basso consentono una variazione continua della tensione in uscita la velocità di variazione della tensione in uscita dipende dalla durata della pressione sul tasto all aumentare del tempo la velocità di variazione della tensione di uscita aumenta progressivamente Nel caso si voglia settare una determinata tensione in uscita si può usare il tastierino numer...

Page 51: ...seconda della natura del carico collegato nel caso di carichi resistivi la potenza e quella nominale nel caso di carichi puramente induttivi questa sale nel caso di carico puramente capacitivo la potenza diminuisce Per cambiare la portata si preme il tasto corrispondente alla portata desiderata posizionato sulla parte sinistra del pannello di comando alla voce RANGE VOLT Quando si cambia portata i...

Page 52: ...tastierino numerico di programmazione Per settare la frequenza tramite il tastierino numerico di programmazione si procede come per la tensione premendo al posto del tasto VOLT il tasto FREQ per indicare all HPS che si vuole programmare la frequenza Anche qui dopo la pressione del tasto ENTER il display relativo alla visualizzazione degli hertz lampeggia fino all avvenuto aggancio della frequenza ...

Page 53: ...ramite i tasti 4WIRES e 2WIRES alla voce SENSE Si noti che l HPS corregge cadute di tensione sui collegamenti fino al 10 della tensione impostata per prevenire eventuali surriscaldamenti della linea stessa superato questo limite l HPS non garantisce che il valore della tensione in uscita sia pari alla tensione impostata e viene visualizzato un segnale di errore vedi ALLARMI DI TENSIONE 2 7 2 TIPO ...

Page 54: ...l HPS si blocca e si accende il led INVERTER 2 8 3 ALLARME DI CORRENTE L HPS opera un controllo della corrente in uscita ciò consente all HPS di poter sopportare per un tempo indefinito il cortocircuito dell uscita L HPS nel caso di carichi che assorbono una corrente superiore di quella nominale opera una limitazione della corrente stessa Questa limitazione viene visualizzata tramite il led LIMIT ...

Page 55: ...a il relativo comando 4 Impostare il modo della macchine remoto range sensing 5 Abilitare gli eventuali teleruttori di linea 6 Sistema disponibile per rampe tensione frequenza 2 9 2 CAMBIO CONFIGURAZIONE MASTER SLAVE Sotto indicati gli step da rispettare per il cambio modo del sistema 1 Portare a 0 la tensione delle macchine interessate al cambio 2 Disabilitare gli eventuali teleruttori di linea 3...

Page 56: ... essersi verificati durante la spedizione Conservare tutti i materiali di imballaggio nel caso in cui il prodotto debba essere restituito un giorno Se si riscontrano danni si prega di presentare immediatamente un reclamo al corriere Non restituire il prodotto in fabbrica senza aver ottenuto la preventiva accettazione dell Autorizzazione al Reso Merce RMA da parte di ELETTROTEST S P A ...

Page 57: ...l corto terra e neutro di uscita qualora si utilizzi la configurazione parallelo vedere lo schema sotto Alla fine chiudi il pannello d uscita I cavi di Potenza e di segnale non vanno cablati assieme I comandi master slave sono tutti a 230V si deve utilizzare un cavo schermato qualora li si cabli con i cavi di segnale INGRESSO INPUT 1 2 3 4 L1 L2 L3 PE AUX MASTER SENSE OUT 3 FASE AUX SLAVE AUX MAST...

Page 58: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 21 3 1 3 CABLAGGIO DEI SEGNALI ...

Page 59: ...deguato alle caratteristiche nominali della macchina vedere paragrafo 5 1 La macchina può assorbire più di 100mA in alta frequenza assicurarsi che il differenziale abbia il filtro in alta frequenza 3 4 PROTEZIONI MAGNETOTERMICHE La protezione magnetotermica è atta a proteggere la linea di alimentazione da cortocircuiti che intervengono a valle della protezione stessa Generalmente dipende oltre che...

Page 60: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 23 3 5 2 Schema di cablaggio monofase trifase configurazione 2 fili ...

Page 61: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 24 3 5 3 Schema di cablaggio monofase trifase configurazione 4 fili ...

Page 62: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 25 3 5 4 Schema di cablaggio trifase configurazione 2 fili ...

Page 63: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 26 3 5 5 Schema di cablaggio trifase configurazione 4 fili ...

Page 64: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 27 3 5 6 Schema di cablaggio trifase configurazione 2 fili MASTER SLAVE ...

Page 65: ...10 02 22 User Manual HPS P 20kVA 6200591_01_ 28 3 5 7 Schema di cablaggio trifase configurazione 4 fili MASTER SLAVE ...

Page 66: ...seriale ad HPS BAUD RATE 1200 nella versione standard DATA BITS 8 STOP BITS 1 4 1 2 Cavo seriale Il cavo seriale utilizza lo standard definito nella figura sottostante 4 2 TABELLA DI ESISTENZA HARDWARE E PROTOCOLLI La tabella di esistenza tra hardware porte di comuncazione e protocolli utilizzabili è mostrata qui sotto Modelli Porte di Comunicazione Protocolli RS232 RS485 LAN Elettrotest Elettrote...

Page 67: ...quinamento ambientale 3 Immunità contro le sovratensioni Categoria II Massima corrente di ingresso 500 Arms PF ingresso 0 82 1 Frequenza di ingresso 50Hz 60Hz Tipo di uscita Trifase Isolamento uscita Isolato Massima tensione di uscita 300V 150V Massima potenza d uscita 200KVA Massima potenza di spunto 3 secondi 360KVA Intervallo di frequenza di uscita 50Hz 80Hz 2 3 Dimensioni 1800 1600 1000 Peso 1...

Page 68: ...Manual HPS P 20kVA 6200591_01_ 31 4 4 3 3 3 3 3 3 Tutte le misure sono in millimetri 1 Interruttore accensione 2 Ventilatore 3 Griglie 4 Pannello connessioni 5 2 DISEGNI MECCANICI 5 2 1 HPS P 200K 1 2 2 2 3 3 3 2 2 2 ...

Page 69: ...nual HPS P 20kVA 6200591_01_ 32 5 3 DIAGRAMMI 5 3 1 TENSIONE MASSIMA IN FUNZIONE DELLA FREQUENZA 5 3 2 CORRENTE DI SPUNTO E TEMPO 0 00 0 50 1 00 1 50 2 00 2 50 3 00 3 50 0 0 10 0 20 0 30 0 40 0 50 0 60 0 Time sec I Io ...

Page 70: ...0 Linea ausiliaria 230V 5x20 5 HT 250V F11 F12 Scheda relè 5x20 2 5 HT 250V F13 F14 Scheda controllo 5x20 2 5 HT 250V F15 F16 Linea aus inverter L1 5x20 2 5 HT 250V F17 F18 Linea aus inverter L2 5x20 2 5 HT 250V F19 F20 Linea aus inverter L3 5x20 2 5 HT 250V F21 F22 Non usati 5x20 2 5 HT 250V 5 5 Accessori 5 5 1 99116963 HPS200K Descrizione Pezzi 1 FUSIBILE NH3 630A GG 690V 2 2 FUSIBILE 10x38 4A A...

Page 71: ...er cambiare i tifosi 40000 Ore per cambiare i condensatori Da 7 a 10 anni per la manutenzione generale Le ore di funzionamento del tuo HPS Ppossono essere controllate via remoto oppure nel display all accensione della macchina Si ricorda che è necessario restituire la macchina a ELETTROTEST S P A per la manutenzione programmata 6 2 RIPARAZIONE E DIAGNOSI ALLARMI Se vengono visualizzati uno o più a...

Page 72: ...ensione che deve essere 230V 10 per macchine monofase e 400V 10 per macchine trifase Fusibile azionato Controlla tutti I fusibili Assorbimento Potenza dall EUT Il TPS T non accetta Potenza dall EUT Cause Solution Copertura ventole Verificare che tutte le parti di ventilazione non siano e coperte e che i filtri dell aria siano puliti Malfunzionamento ventole Controllare il corretto funzionamento de...

Page 73: ...e 2 4 fili errata Verificare con gli schemi la tensione all interno della macchina L interruttore termico è chiuso quando non è in allarme Limitazione della corrente di uscita Controllare la tensione e la corrente di uscita Calibrazione La macchina è fuori calibrazione Si prega di contattare il service ELETTROTEST Cause Solution Sovraccarico Controllare la tensione e la corrente di uscita rimuover...

Page 74: ...pre accompagnare lo strumento in caso di verifica periodica 8 REVISIONE Elettrotest Spa è impegnata in un programma di miglioramento continuo dei prodotti e delle informazioni verso il cliente Si riserva quindi di apportare modifiche alla documentazione e alle specifiche senza preavviso declinando ogni responsabilità per eventuali dati inesatti Rev Data Descrizione 01_ 03 02 22 Aggiunte note manut...