10/02/22
User Manual HPS/P/20kVA 6200591_01_
30
5.
TECHNICAL SPECIFICATIONS
5.1.
DATA SHEET
MODEL
200K
Power supply
3PH 400Vac ±10%
Power
200KVA
International Protection
IP20
Pollution degree
3
Overvoltage category
Category II
Maximum input current
500 Arms
Input frequency
50Hz
–
60Hz
Input PF
>0.82
(1)
Output type
Three phase
Output isolation
isolated
Maximum output
voltage (RMS)
300V /150V
Maximum output
POWER
200KVA
Maximum output
inrush current (3 sec)
360KVA
Output frequency range
50Hz
–
80Hz
(2) (3)
Dimensions
1800 : 1600 : 1000
Weight
1800 kg
Protections
OVP,UVP,OTP,OCP
Operating temperature
0 / +35 °C
Storage temperature
-20 / +70 °C
RS232
Yes
RS485
Option
LAN
Option
Safety certification
EN 61010-1
EMC certification
EN 61000-6-2
(4)
EN 61000-6-4
(5)
(1)
At maximum power
(2)
Under 50Hz there is derating of maximum voltage.
(3)
you can set up 320Hz with the derating of the performance
(4)
Immunity: industrial environment.
(5)
Emission: industrial environment.