Elgar CW-M Series
3.6 Power Out Connections
1. Remove the protective cover from the terminal block.
2. A factory jumper has been added to connect NEUTRAL to GROUND.
If the front connector requires LINE and NEUTRAL to be reversed, move
this jumper to connect LINE to GROUND. See Figure 3–7 below. Most loads
require NEUTRAL to be grounded.
The factory jumper may be removed if the load has a GROUND or if LINE or
NEUTRAL voltages are held to less than 500 VRMS with respect to chassis.
3. Reinstall the protective cover on the terminal block.
WARNING!
Verify that the load is set up to be LINE GROUNDED
or NEUTRAL GROUNDED. (Equipment with polarized plugs
requires NEUTRAL to be grounded.)
Figure 3–7 Output Power Connections
20
Summary of Contents for CW 1251M
Page 2: ......
Page 3: ......
Page 4: ......
Page 6: ...ii This page intentionally left blank...
Page 12: ...Elgar CW M Series This page intentionally left blank 2...
Page 24: ...Elgar CW M Series Figure 3 2 Mounting Dimensions Front and Rear Views CW 801M CW 1251M 14...
Page 25: ...Elgar CW M Series Figure 3 3 Mounting Dimensions Front and Rear Views CW 2501M 15...
Page 26: ...Elgar CW M Series Figure 3 4 Mounting Dimensions Top and Side Views CW 801M CW 1251M 16...
Page 27: ...Elgar CW M Series Figure 3 5 Mounting Dimensions Top and Side Views CW 2501M 17...
Page 34: ...Elgar CW M Series This page intentionally left blank 24...
Page 38: ...Elgar CW M Series 4 3 2 Setup for Six in Parallel Configuration 28...
Page 39: ...Elgar CW M Series 4 3 3 Setup for Six Phase Configuration 29...
Page 40: ...Elgar CW M Series 4 3 4 Setup for Two Phase Configuration 30...
Page 42: ...Elgar CW M Series This page intentionally left blank 32...
Page 48: ...Elgar CW M Series This page intentionally left blank 38...