Installation and First Start-Up
- 24 -
10.2
Check of Safety Relevant Configuration
Before installing the LIMAX33 CP-00, the technician must ensure that the safety-relevant configuration specified
on the info sheet belonging to the LIMAX33 CP-00 complies with the relevant lift conditions. If this is not the
case, the LIMAX33 CP-00 must not be used for this lift. Instead, a LIMAX33 CP-00 with suitable configuration
must be acquired, or a still empty LIMAX33 CP-00 must be programmed with suitable configuration.
10.3
Mechanical Installation
PLEASE NOTE:
There is a separate mounting instruction for the installation of the magnetic tape and the
LIMAX33 CP-00 which has to be observed (
The cables for the supply, inputs/outputs (PIO cable) as well as for the safety circuit and the actuators (SCA
cable) must be laid with mechanical protection.
10.4
Electrical Installation
10.4.1
Basic Design
The complete system LIMAX33 CP-00 consists of:
the LIMAX33 CP-00 sensor head
(measuring system electronic, logic and safety relevant and not safety relevant interfaces)
the magnetic tape AB20-80-10-1-R-D-15-BK80
the mounting kit for the magnetic tape
and the tape presence detector
The figure on the next page shows the top side and bottom side view of the LIMAX33 CP-00. There are two
versions of LIMAX33 CP-00: One version with eSGC (refer to Figure 6) and one without eSGC. On the version
without eSGC, the M12 connector is not fitted and the assignment of the LEDs is different.
“eSGC” is an abbreviation for “electronic Safety Gear Contact”. This actuator-contact is implemented by solid
state switches (therefore “electronic”). The eSGC actuator (also referred as “SGC” in this manual) is intended to
act an accordingly suitable safety gear, a blocking device of a speed governor or another braking element –
except the brake handled via safety circuit – e.g. a rope gripper. The braking element for eSGC is electrically
connected to the LIMAX33 CP-00 via a connector on the top side.
If an eSGC actuator is needed according to the safety functions, the system should fulfill (
14.1.3), the version
with eSGC must be used. If no eSGC actuator is needed according to the safety functions, the system should
fulfill, it is arbitrary if a system with eSGC (eSGC actuator disabled in this case) or a system without eSGC is
used.
Other actuator contacts are: OC, SR1 and SR2. They are implemented as dry contacts between each two wire
ends of the SCA-cable (see below). They are intended to be wired in the safety circuit (