H O W T O C O N N E C T P O W E R ( 1 2 0 V )
16
Use U.L. Listed Conduit for
Supplying Power to the Unit
Suggestion:
Seal all open holes of
electronic box with
sealant when finished
wiring.
Do Not Use This Outlet Unless You Are
An Authorized Service Technician
Minimum:
15-amp
breaker
switch per
operator
needed
Gate Operator MUST be Properly Grounded
Caution: ELITE ACCESS SYSTEMS, INC. is not responsible for conflicts between the information listed in the above chart and the requirements
of your local building codes. The information is for suggested use only. Check your local codes before installation.
White Wires (Neutral)
Black Wires (120 VAC)
Green Wires (Ground)
16 Gauge
150 Feet
14 Gauge
250 Feet
12 Gauge
400 Feet
10 Gauge
650 Feet
8 Gauge
1000 Feet
4 Gauge
2200 Feet
WIRE GAUGE REQUIREMENT FOR 120 VAC POWER SUPPLY: 1/2 HP AND DUAL MOTOR ONLY
W4
OFF
ON
OFF
ON
Earth Ground Rod Installation
12 gauge wire
Elite Access Systems is not responsible for improper
installation or failure to comply with all necessary local
building codes.
8 ft
The earth ground rod must be located within 3 feet of the Elite gate
operator. Use the proper type earth ground rod for your local area.
The ground wire
must
be a single, whole piece of wire.
Never
splice two
wires for the ground wire. If you should cut the ground wire too short,
break it, or destroy its integrity, replace it with a single wire length.
Proper grounding gives an electrical charge, such as from an electrical static
discharge or a near lightning strike, a path from which to dissipate its energy safely
into the earth.
Without this path, the intense energy generated by lightning could be directed
towards the Elite gate operator. Although nothing can absorb the tremendous power
of a direct lightning strike, proper grounding can protect the gate operator in most
cases.
Before digging more than 18" deep, contact local underground utility companies.
Avoid damaging gas, power, or other underground utility lines.