PAR.

DESCRIPTION

RANGE

DEFAULT

VALUE*

LEVEL**

U.M.

dPO

Determines when instrument starts up if  
the defrosting cycle must be activated (if the 
temperature on the evaporator allows this) 
y=defrosting activated at start-up 
n=defrosting not activated at start-up

n/y

n

1-2

flag

tcd

minimum time for each compressor state 
before defrosting “Ontime if >0; “Offtime if >0

-31...31

0

2

min

Cod

Compressor “Off” time before defrost cycle. 
The compressor is not  turned on if a defrost cycle
is expected in the time indicated by the parameter.
0=Function excluded

0...60

0

2

min

Defrosting controller

-dEF label

NOTE:   At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the 

level 2 parameters. The symbol 1-2 indicates the parameters that are displayed at both menu levels

Alarms-AL label

Att

Determines if “LAL” and “HAL” are expressed as 
absolute values or as a differential related to the 
set point 
0=absolute value 
1=value related to set point

0/1

0

2

flag

AFd

Alarm differential

1.0...50.0

2.0

1-2

°C/°F

HAL   (2)

Maximum alarm. Temperature limit (whose 
absolute or relative value status is regulated by 
“Att”) above which the alarm is activated.

LAL...150.0

50.0

1-2

°C/°F

LAL   (2)

Minimum alarm. Temperature limit (whose 
absolute or relative value status is regulated by 
“Att”) below which the alarm is activated.

-50.0...HAL

-50.0

1-2

°C/°F

PAO  (3)

Alarm exclusion time after start-up of instrument 
following a power failure

0...10

0

1-2

hours

dAO

Alarm exclusion time after defrosting

0...999

0

1-2

min

EWDR 981 

5/8

OAO

High and low temperature alarm delay after 
disabling digital input
(door closed)

0...10

0

2

hours

tdO

Time out after alarm signal when

digital input is 

disabled (door open)

0...250

0

2

min

tAO  (3)

Temperature alarm delay time

0...250

0

1-2

min

EAL

External alarm to lock controllers 
n=does not lock, 
y=locks

n/y

n

2

flag

AOP

Polarity of alarm output: 
0 = alarm active and output disabled; 
1 = alarm active and output enabled

0/1

1

2

flag

PbA

Configuration of temperature alarm on 
probe 1 and/or 3: 
0=on probe 1 (thermostat control) 
1=on probe 3 (display) 
2=on probe 1 and 3 (thermostat control and display) 
3=on probe 1 and 3 (thermostat control and display) 

on external threshold

0/1/2/3

0

2

num

SA3

Probe 3 alarm set point

-50.0...150.0

50

2

°C/°F

dA3

Probe 3 alarm differential

-30.0...30.0

2.0

2

°C/°F

dt

Dripping time

0...250

0

1-2

min

Light & digital inputs

Lit Label

dLt

Light relay disabling delay after closing 
door if “dSd”=y

0...31

0

2

min

OFL

Light relay disabled even if disabling delay 
“dLt” is active

n/y

n

2

flag

dAd

Delay in activating digital input

0...255

0

2

min

dOd

Digital input switches off loads

n/y

n

2

flag

dSd

Light relay enable from door switch. 
n = door open, light does not turn on; 
y = door open, light turns on (if it was off)

n/y

y

2

flag

Summary of Contents for EWDR 981

Page 1: ... main menu level The set point setting folder is also closed when the time out elapses Alarm on If an alarm condition exists when the Machine Status menu is accessed the ALfolder label appears PARAMETER PROGRAMMING MENU Access the menu by pressing the set button for at least 5 seconds The menu structure enables all parameter folders to be divided into two levels All the level 1 folders can be acce...

Page 2: ...eter OFL Y DIAGNOSTICS PROBE ALARMS When one of the probes is outside the nominal operating range or the probe is open or has shorted an alarm is generated if at least one of these conditions persists for at least 10 seconds If at least one of these 3 alarms is signalled the alarm LED and relay are enabled When activated code E1 appears on the display If several alarms are activated at the same ti...

Page 3: ...ded using an ordinary bipolar cable note that if probes are extended this affects the electromagnetic compatibility EMC of the instrument special care must be used when wiring The TTL serial cable must be kept separate from the power cables EWDR 981 3 8 CONDITIONS OF USE PERMITTED USE For safety reasons the instrument must be installed and used in accordance with the instructions supplied Users mu...

Page 4: ... min dbi Delay between switch ons the specified time must elapse between two subsequent switch ons 0 250 0 1 2 min OdO Delay in activating outputs after start up of instru ment or after a power failure Not active if 0 0 250 0 1 2 min dty Type of defrost 0 electrical defrosting 1 cycle reversing defrosting hot gas 2 Free mode defrosting compressor disabled 0 1 2 0 1 2 num dit Period of time elapsin...

Page 5: ...is regulated by Att below which the alarm is activated 50 0 HAL 50 0 1 2 C F PAO 3 Alarm exclusion time after start up of instrument following a power failure 0 10 0 1 2 hours dAO Alarm exclusion time after defrosting 0 999 0 1 2 min EWDR 981 5 8 OAO High and low temperature alarm delay after disabling digital input door closed 0 10 0 2 hours tdO Time out after alarm signal when digital input is d...

Page 6: ...to temperature displayed that is also used by controllers 0 1 2 2 2 num LdL Minimum value that can be displayed 55 0 140 50 0 2 C F HdL Maximum value that can be displayed 50 0 302 140 0 2 C F ddL display during defrosting 0 displays temperature read by thermostat control probe 1 displays temperature read entering defrost cycle until set point is reached 2 displays dEF label during defrosting unti...

Page 7: ...s set to positive values and the parameter LAL is set to negative values LAL 3 Refers exclusively to high and low temperature alarms 4 when changing from C to F or vice versa the set points differentials etc are NOT converted for example set 10 C becomes set 10 F 5 CAUTION positive or negative values change polarity Positive values active input when contact is closed Negative values active input w...

Page 8: ...NG DIAGRAM TERMINALS 1 2 Probe input 1 room probe 1 4 Probe input 3 display or 2nd evaporator probe 5 6 Digital input 1 5 7 Digital input 2 8 9 Auxiliary output 12Vc 20mA E see par H25 alarm default 13 14 Power supply 230Va A TTL input for Copy Card 20 21 22 N O relay output C see par H21 compressor default 19 22 N C relay output C see par H21 compressor default EWDR 981 1 2 4 5 6 7 8 9 10 11 12 1...

Reviews: