background image

To access the Machine Status menu, press
the “set” button and quickly release it. 
If no alarms are present, the label “SEt”
appears.  By using the “UP” and “DOWN”
buttons you can scroll through the other
folders in the menu: 
-AL: alarm folder (if alarms present, except
for faulty probes/probe errors;
-SEt: Set point setting folder. 
-rtc: Real Time Clock folder
-Pb1: probe 1 value folder;
-Pb2: probe 2 value folder;
-Pb3: probe 3 value folder (if present);

Set setting

Access the “Machine Status” menu, press
the “set” button and quickly release it. The
“Set” folder label appears. To display the
Set point value, press the “set” button
again. 
The Set point value appears on the display.
To change the Set point value, use the
“UP” and “DOWN” buttons within 15 sec-
onds. If the parameter is LOC = y the Set
point cannot be changed.

Alarm on

If an alarm condition exists when the
Machine Status menu is accessed the “AL”
folder label appears (see section on
“Diagnostics”).

Real Time Clock

By pressing the “set” button when the
“rtc” label appears, the label d00 (days) is
displayed. Use the “UP” and “DOWN” but-
tons to set days. If you do not use the but-
tons for over 2 seconds or if you press
“set” you switch to the hours (h00) and
minutes (‘00) folders: use the “UP” and
“DOWN” buttons to set the hours and
minutes respectively. If you do not use the
keyboard for over 15 seconds (time-out)
or if you press the “fnc” button once, the
last value shown on the display is con-
firmed and you are taken back to the pre-
vious screen mask.

NOTE: Always use the “set” button to
confirm the hours/minutes/days setting.
NOTE2: We recommend considering the
first day d00 as SUNDAY.

Displaying probes

If you press the “set” button when the
corresponding label appears, the value of
the probe associated with it is displayed.

FnC FUNCTION FOLDER 
The FnC folder (last folder visible from
the Programming Menu, level 1) con-
tains the following functions. 
They are activated using the “set” but-
ton

If the unit is switched off, the function
labels go back to their default status.

ACTIVATING MANUAL DEFROST CYCLE

To activate the defrost cycle manually,
press the “UP” button (if configured =1)
for 5 seconds. If the right defrosting con-
ditions are not present (the temperature
of the evaporator probe is higher than the
end of defrost temperature, for example)
or parameter OdO different than 0, the
display will flash three (3) times to indicate
that the operation will not be performed.

ADVANCED FUNCTIONS

DOOR SWITCH INPUT

This is a clean contact digital input with
programmable polarity. 

The door switch input functions are con-
trolled by the values of the following para-
meters:

If activation state forcing is enabled (dOA
is not 0), the compressor and/or fan out-
puts can be activated when the time set in
parameters dCO and dFO expires.

Parameter H11 is used to configure the
digital input with values between -9 and
+9. Positive and negative values are used
to select the polarity assigned to the input
and:

NOTE: 
the sign “-” indicates that the input is
activated when the contact is closed
The ‘+’ sign indicates that the input is
activated when the contact is open

DEVICE STAND-BY CONTROLLER

This controls the operating mode of the
device when it is on stand by according to
the following parameters: 

The Stand-by controller can be digital input
or button enabled if suitably configured. 
The status of the instrument when on
stand-by is determined by the value of
parameter H08. Three possible operating
modes are defined:

EXAMPLE 1

: the display is off and the con-

trollers active, the instrument signals any
alarms by reactivating the display - OFF DIS-
PLAY

EXAMPLE 2

: the display is off and all the

controllers, including the alarms, are also
disabled  - STAND-BY

EXAMPLE 3

: the display shows the “OFF”

label and all the controllers, including the
alarms, are also disabled- STAND-BY

LINK

The Link function is used to connect up to
8 instruments (1 Master device and 7 slave
devices). The distance between one device
and another must be 7 metres maximum
whereas the maximum distance between
the first and last instrument in the network
must be approximately 50m.

NOTE

: the serial link between the devices is

powered.

Master

Instrument that controls the networks and
sends commands to the Slaves. The Master
is selected using parameter L00 (the value 0
defines the Master)

Slave

Instrument(s) with own controllers that also
perform(s) commands issued by the Master
(with parameters L03..L06).

Echo

This only displays the values of the instru-
ment that it is associated with (it does not
therefore have its own I/O resources but
only serves as a repeater). 

NOTE

: only one Echo can be connected to

anyone instrument. 

Defrosting

The Link network controls defrosting. The
Master sends the defrost command which
can be performed synchronously (at the
same time) or sequentially (one defrost
after another) without affecting the normal
protections or delays for each instrument
(see parameter L03).

Other Functions

The Master can also activate the functions
associated with buttons or the Digital Input
for all the Slaves: switching lights on/off,
alarm silencing, auxiliary set point, auxiliary
relay, stand-by (on/off) and functions relat-
ed to Night & Day controller (see parame-
ter L05). 
The Master can also synchronize the Slave
(or Echo device) displays with the Master
device display (see parameter L04). 
NOTE: synchronized defrosting refers to
actual defrosting and not to dripping and
subsequent defrosting. The defrost LED on
the Slave units blinks when synchronized
defrosting has terminated and the Slaves
are awaiting for the thermostat control to
be enabled by the Master. 
The functions are associated with the
instruments by correctly setting the para-
meters (see the parameter table for the
“Lin” label folder)

ID 985/S/E/CK - ID985/E LX

3/14

Function

Reduced set point 
Aux 
Pressure switch alarm reset

**default

Function label

NOT ACTIVE

SP** 
AoF 
rAP

Label

Function
ACTIVE

OSP 
Aon 
rAP

Par

Description

PAO

alarm exclusion at start-up 

OdO

Output delay from power-on 

H08

Operating mode in stand-by.

Par

Description

dOd          Digital input switches off loads 
dAd

D.I. activation delay 

OAO

Alarm signal delay after disabling the digi-
tal input (door closed)

tdO

Time out door open. Time out signalled
when D.I is activated. 
(door open)

dOA

Forced behaviour from 
digital input

PEA

Enables forced behaviour from door
switch and/or external alarm 

dCO

Delay in enabling compressor with 
consensus 

dFO

Delay in enabling fans with 
consensus 

H11

Digital output configurability/polarity 1 

H21...H25

Digital output configurability 1...5

Summary of Contents for ID 985

Page 1: ...t point is entered set point ON for setting set point Compressor or relay 1 ON for compressor on blinking for protection delay or enabling blocked Defrosting ON when defrosting in progress blinking when activated manually or by digital input Alarm ON for active alarm blinking for silenced alarm Fans ON when fan is on aux ON when auxiliary output is operating aux fnc set ID985 E LX aux set fnc UP b...

Page 2: ...ed if it is not successful n will be displayed Download from reset Connect the copy card when the instrument is OFF The program ming parameters are downloaded when the device is switched on At the end of the lamp test the following messages are dis played for about 5 seconds dLY label if copy operation is successful DLn label if operation fails NOTE after the parameters have been downloaded the de...

Page 3: ...hen it is on stand by according to the following parameters The Stand by controller can be digital input or button enabled if suitably configured The status of the instrument when on stand by is determined by the value of parameter H08 Three possible operating modes are defined EXAMPLE 1 the display is off and the con trollers active the instrument signals any alarms by reactivating the display OF...

Page 4: ...r loads are immediately deactivated the alarm LED lights up to signal tripping and the label nPA in the alarm folder appears on the display Controlling is performed using 2 parame ters PEn and PEI nPA is a subfolder of AL Alarms and keeps a record of each time the pressure switch is activated if the value indicated by PEn is reached in a period of time that is less than or equal to PEI the label n...

Page 5: ...so signalled for address ing conflicts when a the number of Slaves set on the MAS TER is different from the actual number of Slaves on the network b 2 or more Slaves have the same address ELECTRICAL CONNECTIONS Warning Always switch off machine before working on electrical connections The instrument has screw terminals for connecting electrical cables with a maxi mum diameter of 2 5 mm2 only one c...

Page 6: ... or after a power failure Not active if 0 0 250 0 1 2 min dty Defrost type 0 Electrical or Off Cycle defrost Compressor OFF during Defrost 1 Reverse cycle defrost hot gas Compressor On during Defrost 2 Free Independent defrost compressor cycles ON OFF according to temperature during defrost 0 1 2 0 1 2 flag dit Period of time elapsing between the start of two defrosts 0 function disabled 0 250 6 1...

Page 7: ...y all the level 1 parameters At level 2 the folders will only display all the level 2 parameters The level marked 1 2 allows the parameter to be displayed at both levels FAd Fan activation intervention differential see FSt Fot 1 0 50 0 2 0 1 2 C F Fdt Delay before fan activation after defrosting 0 250 0 1 2 min dt Dripping time 0 250 0 1 2 min FCO Disables fans with compressor off Off y fans activ...

Page 8: ...f disabling delay dLt is active n y n 2 flag dAd Delay in enabling digital input 0 255 0 2 min dOd Digital input switches off loads n y n 2 flag Att Determines if LAL and HAL are expressed as absolute values or as a differential related to the set point 0 absolute value 1 value related to set point 0 1 0 2 flag AFd Alarm differential 1 0 50 0 2 0 1 2 C F HAL 4 Maximum alarm Temperature limit whose...

Page 9: ...lag L04 Refers to Slave only Distributed display n Slave displays local values y Slave displays Master display n y y 2 Flag L05 Activation of Master network functions n does not ask Slaves for activation of remote functions y asks Slaves for activation of remote functions Slave n ignores activation of remote functions from Master y accepts activation of remote functions from Master n y n 2 Flag L0...

Page 10: ...d by operating mode 0 only display switched off 1 display on and controls locked 2 display off and controls locked 0 1 2 2 2 num H12 6 Configuration of digital inputs polarity Same as H11 9 9 0 2 num Configuration CnF label H02 Quick activation time for functions with configured buttons Not possible for aux time expected 1 second 0 15 5 2 sec H06 Button input aux door switch light active when inst...

Page 11: ...eter 1 2 1 2 Copy Card Fpr label UL Transfer of parameter map from instrument to Copy Card dL Transfer of parameter map from Copy Card to instrument 1 1 Fr 8 Formatting Cancels all data in the Copy Card 1 NOTES 1 See Duty Cycle page 4 3 If relative values are present par Att 1 parameter HAL is set to positive values and the parameter LAL is set to negative values LAL 4 Refers exclusively to high a...

Page 12: ...oduced by the probe is added to any error that is characteristic of the instrument RS485 RS485 Personal Computer PCI1110 1120 TelevisCompact TelevisStation RS485 BusAdapter TTL Personal Computer PCI1110 1120 TelevisCompact TelevisStation BusAdapter130 150 TTL RS 485 serial interface on DIN rail for connecting the device and an RS 485 network designed for connection to Televis or ModBUS supervision...

Page 13: ... 5 2 A 1 4 hp 250Va B C D SPST 3A 250Va A SPDT 8 3 A 1 2 hp 250Va B C SPST 8 3 A 1 2 hp 250Va D SPST 5 2 A 1 4 hp 250Va if present from 55 to 140 C better than 0 5 of bottom scale 1 digit 1 or 0 1 C 2 5W 3VA 12 24Va 12 36Vc 10 or 95 240Va 10 12Va 10 50 60 Hz from instrument it is connected to 1 2 3 4 5 6 7 8 9 10 14 15 16 17 18 19 20 A B C D LINK POWER SUPPLY TTL ECHO GND RS 485 LINK Pb2 Pb1 Pb3 D...

Page 14: ...VE 1 L00 0 ECHO SLAVE 2 L00 0 ECHO SLAVE 3 L00 0 code 9IS23080 GB rel 4 08 Eliwell Controls s r l 2008 All rights reserved Eliwell Controls s r l Via dell Industria 15 Zona Industriale Paludi 32010 Pieve d Alpago BL ITALY Telephone 39 0437 986 111 Fax 39 0437 989 066 Sales 39 0437 986 100 Italy 39 0437 986 200 other countries E mail saleseliwell invensyscontrols com Technical helpline 39 0437 986 ...

Reviews: