ID 985/S/E/CK - ID985/E LX
7/14
PAR.
DESCRIPTION
RANGE
DEFAULT
VALUE*
LEVEL**
U.M.
dPO
Determines when instrument starts up if the
defrosting cycle must be activated (if the tempera-
ture on the evaporator allows this)
y=defrosting activated at start-up
n=defrosting not activated at start-up
n/y
n
1-2
flag
tcd
Minimum time for each compressor state before
defrosting “Ontime if >0; “Offtime if >0
-31...31
0
2
min
Cod
Compressor “Off” time before defrost cycle. The
compressor is not turned on if a defrost cycle is
expected in the time indicated by the parameter.
0=Function excluded
0...60
0
2
min
F
an controller
-F
An label
Defrosting controller
-deF label
FPt
Determines if “FSt” and “Fot” are expressed as
absolute values or in relation to set point
0=absolute value; 1=value related to set point
0/1
0
2
flag
FSt
Fan stop temperature. Temperature limit that, if
exceeded by the value read by the evaporator
probe, stops the fans.
-50.0...150.0
2.0
1-2
°C/°F
Fot
Fan start temperature. If the temperature read by
the evaporator probe is lower than the set value
the fans remain off.
-50.0...150.0
-50.0
2
°C/°F
NOTE: At level 1 the folders will only display all the level 1 parameters. At level 2 the folders will only display all the
level 2 parameters. The level marked 1-2 allows the parameter to be displayed at both levels.
FAd
Fan activation intervention differential.
(see “FSt”, “Fot”)
1.0...50.0
2.0
1-2
°C/°F
Fdt
Delay before fan activation after defrosting
0...250
0
1-2
min
dt
Dripping time
0...250
0
1-2
min
FCO
Disables fans with compressor off
(Off)
y = fans active (with thermostat; in response to
value read by defrost probe, see “FSt” parameter);
n = fans off;
dc = duty cycle (using parameters “Fon” and “FoF”
n/y/dc
y
1-2
flag
dFd
Disables evaporator fans.
y=fans disabled
n=fans enabled
y/n
y
1-2
flag
Fod
Enables fan stop with door open and fan re-start
when door is closed (if fans were on).
n=fans stop;
y=fans unchanged
n/y
n
2
flag
FdC
Fan shut-down delay after compressor stop
0=function excluded
0...99
0
2
min
Fon
Fan start-up time in Duty mode
Cycle; valid for FCO=dc
0...99
0
2
min
FoF
Fan shut-down time in Duty
Cycle; valid for FCO=dc
0...99
0
2
min
“dd (2)
dE1...dE8; daily defrost start time
0...23/0...59
24
1
hours/min
“Fd (2)
F1...F8 festive defrost start time
0...23/0...59
24
1
hours/min
(3)
SCF
Condenser fan set point
-50.0...150.0
10
2
°C/°F
dCF
Condenser fan differential
-30...30
2
2
°C/°F
tCF
Condenser fan start-up delay after defrost
0...59
0
2
min
dCd
exclusion of condenser fans in defrost mode
n/y
y
2
Flag