9MA10011
17/52
4.4.2 Analogue alarms
This menu shows the list of onboard analogue inputs.
4.4.2
ANALOGUE ALARMS
01
ONBOARD-P1
|
02
ONBOARD-P2
|
03
ONBOARD-P3
|
04
ONBOARD-P4
|
05
ONBOARD-P5
|
06
ONBOARD-P6
|
07
ONBOARD-P7
|
08
ONBOARD-P8
Select the required analogue input using the UP and DOWN keys and press OK.
A page displaying the following information will open:
(example Index 01 Input, pressure probe)
4.4.2
ANALOGUE ALARMS
Index
1/8
|
Name
ONBOARD-P1
|
Alarm Output
1
|
Delay (min)
0
|
Positiv. Emerg.
10.0
|
Positiv. Delay
8.0
|
Negativ. Emerg.
0.0
|
Negativ. Delay
0.0
|
Alarm Hysteresis
0.1
•
Index
: Input Index***
•
Name
: Name of Input***
•
Alarm Output
: 0=none associated; 1=Output 1;
•
Delay (min)
: minutes delay before activating Alarm Output [0…240 min]
•
Positiv. Emerg
: upper threshold and immediate generation of alarm when
limit exceeded
•
Positiv. Delay
: upper threshold and delayed generation of alarm when limit
exceeded
- NOTE: Positiv. Emerg. > Positiv. Delay
•
Negativ. Delay
: lower threshold and delayed generation of alarm when lower
limit exceeded
•
Negativ. Emergency
: lower threshold and immediate generation of alarm
when lower limit exceeded
-
NOTE
: Negativ. Emerg. < Positiv. Delay
•
Alarm Hysteresis
: Alarm reset hysteresis.
*** Read-only information.
Notice : alarm thresholds and hysteresis values are expressed in the units of
measure listed above (point 4.4.1 for the Analogue Input).