M1 Cross Platform Controllers - User Guide
Page 25
System Testing
To assure the proper working order, it is recommended that the system be
tested once a week using the following procedure.
CAUTION: If the system
Is monitored by a Central Monitoring Station, always contact them prior
to performing this test.
Secure all protected doors and windows.
1. Enter a valid User code.
2. The Armed and Exit lights will illuminate and the exit tone will start.
At the end of the exit delay the alarm system will be armed Away.
3. Trip the system by opening a protected window.
4. Confirm that the alarm sounding device (bell or siren) activates.
5. Disarm the system to silence the system and return to normal status.
To test the system while also testing the system standby battery:
1. Remove the AC transformer from the AC outlet. It may be necessary
to remove the restraining screw securing the transformer to the wall.
2. The keypad will display AC Trouble after a programmed time delay.
3. Activate the system using steps 1 to 7 listed above.
NOTE: Plug the AC transformer into the AC outlet after the test.
A manual battery load test may be activated without tripping the alarm.
1. Press the ELK key and enter a Master User Code.
2. Press the UP arrow key to find: “
8-System Settings
.”
3. To select this menu press the RIGHT arrow key.
4. Press the UP arrow key to find “
84-System Test
”.
5. To select this menu press the RIGHT arrow key. The Keypad will
display “
1:Battery Test
”.
6. To start the test press the RIGHT arrow key. The battery voltage and
current (amperage consumed by the system) will be displayed. The
battery is OK if it maintains a voltage above 12.2V for the test duration.
If a LOW BATTERY trouble occurs, the battery should be replaced.
Contact the installation company for service.
This control unit was manufactured under rigid quality standards. Mainte-
nance is best performed by the installing company with trained service
personnel.