12.2. Emergency mode 

 

In case a safety device (LSA, LSI, SLA or SLZ) is faulty, emergency mode is possible. 
After a warning time of 10 seconds, the gate can be moved in an emergency mode by 
using BA or BZ (dead man’s function). During the warning time as well as during the 
emergency mode the warning light is flashing. Emergency mode by radio remote control 
BT or BTG) is not possible due to safety reasons. 
 

 Warning

! Even when a safety device is faulty, the gate can be moved by BA and 

BZ. The buttons BA and BZ therefore have to be installed in such a way, that the 
gate can be seen during movement. 

 

Warning! 

Are external devices -giving a constant signal (e.g. timer) - connected to 

BA or BZ, these devices can activate the emergency mode and move the gate 
when a safety feature is faulty or active. 

 

Warning! 

In case the multi-functional relay is used for an additional radio remote 

channel, which is connected to BA or BZ, the emergency mode can be started by 
radio remote control. In this case only fixed transmitters should be used in such a 
way, that the gate can be seen during movement. 

 

13. Technical data MO36 
13.1. Selection range of Parameter and Original settings

 

 

Constant, not changeable values 

Parameter Original 

settings 

Time-lag before reactivating motor 

500ms 

Reversing for a short distance on obstacle 

500ms 

Time-lag before reversing 

200ms 

Max. running time limit   

500s 

Running time reserve during regular mode 

10s 

Warning time prior to emergency mode  

10s 

 

Changeable values 

Parameter 

Selection range 

Original settings 

Running distance 

Max. 32.000 Impulse 

3.000 Impulse 

Force 

1 - 99 

30 

Speed 

Level 1 - 8 

Level 8 

Time lag during opening 

0s - 9s 

2s 

Time lag during closing 

0s - 9s 

5s 

Stay-open time for both wings 

1s - 299s / OFF 

OFF 

Stay-open-time for pedestrian wing 

1s - 299s / OFF 

OFF 

Wind blast suppression 

0s - 9s 

0s 

Warning prior to opening 

0s or 4s 

0s 

Warning prior to closing 

0s or 4s 

0s 

Pressure relief of  
electromagnetic bolt 

0s / 1s / 2s / 90s 

0s 

Multi-functional relay 

Push button mode / Toggle 
mode / Light pulse / 3-minute-
light 

Push button mode 

LS lockage function 

ON / OFF 

OFF 

Photo-cell function 

L1 or L2 or L3 

L1 

Number of wings 

1 / 2 

Photo-cell testing 

ON / OFF 

OFF 

Type of safety contact profile 

8,2k

 or FRABA 

8,2k

 

Radio remote control code BT 

X-code 

- + - + - + - + - 

All other radio remote control codes 

X-code 

deleted 

 

Summary of Contents for TERRA 180

Page 1: ...Installation and operating instructions Swing Gate Opener TERRA 180 182 TERRA 250 252 TERRA 320 322...

Page 2: ...tion plan of the controller MO36 ________________________________________________________22 8 Programming MO36 _________________________________________________________________________25 8 1 Learning...

Page 3: ...s intended During installation initial operation phase maintenance and testing of the controller the individually relevant regulations for safety and accident prevention have to be obeyed These are th...

Page 4: ...d manner the user must ascertain that no danger for himself or others will result from this use He should also ascertain that the planned use will have no detrimental effect on the appliance itself Th...

Page 5: ...on OPEN not required required for wings from2 500mm Power supply 230V 50Hz 230V 50Hz 230V 50Hz Operating voltage 24 V 24 V 24 V Duty cycle 50 50 50 Blocking when open closed Yes Yes Yes Soft Start and...

Page 6: ...g next to the gate either with set 1 or set 2 please use the measurements in the respective installation manual Drawing 1 Drawing 2 Please make sure that the gate wings can be moved easily and that th...

Page 7: ...5 removing of the adjustment clip Warning Please do not leave the emergency release key in the key lock Please do not remove the protective foil and the protective tape before installation has been c...

Page 8: ...plate 3 Support profile 4 Mounting plate 5 Gate support 6 Welding profile 7 Emergency release lever 8 Adjustment clip 4 1 Tools needed The following tools are needed on site for the installation 1 Tor...

Page 9: ...oncrete at least half way up the sides of the housing Note Do not remove the protective foil and the protective tape which covers the gap between the cover plate and the underfloor housing They protec...

Page 10: ...below the gate support see drawing 6 Insert the key and turn it 90 anti clockwise Pull the emergency release lever downwards The gate opener is now released and the gate can be moved freely ATTENTION...

Page 11: ...20 33 4 2 5 Installation at the gate Use the included welding profile There are 4 tapholes at one end of the welding profile The pivot point of the gate is located between these tapholes Pivot point D...

Page 12: ...inge Place the gate with the gate support onto the gearbox shaft which protrudes from the underfloor opener Push the lever up and lock the emergency release with the key see drawing 7 Drawing 9 Move t...

Page 13: ...opens first Max permitted force setting The original setting is force level 30 Change the force settings only when the original settings are not sufficient during learning The max permitted force set...

Page 14: ...ton LERN on the controller for approx 2 seconds The display shows P1 h Press the button LERN again The display now shows 1F i Now select the number of gate wings Confirm the displayed 1F for one wing...

Page 15: ...nto direction CLOSED until the end stop display P2 The gate is now in position CLOSED Should the gate now be in position OPEN the wires 4 and 5 of the motor connection cable at the 5 pin connection ha...

Page 16: ...number of gate wings Push button BT until it displays 2F Confirm the displayed 2F for two wings with the button LERN j The display shows HA manual operation k Now you can move each gate wing separate...

Page 17: ...o direction CLOSED until the end stop display P2 The gate is now in position CLOSED Should the gate now be in position OPEN the wires 4 and 5 of the motor connection cable at the 5 pin connection have...

Page 18: ...ks see 4 8f Adjustment clip Gear shaft Pinion Drawing 11 For perfect operation of the gate system it is now necessary to activate the pressure relief for the electromagnetic bolt a Press the button LE...

Page 19: ...ace the cover plate onto the underfloor housing ATTENTION Tighten the screws only 1 turn unto the point when the thread barely holds the screws Do not fasten the screws completely yet Piece by piece i...

Page 20: ...5 pin connection FAHR or GEH f Insert the adjustment clip from above into the gate opener The level part of the adjustment clip points away from the gear shaft g Make sure the marks on the pinions and...

Page 21: ...will have adverse effect on the motor performance Cross section 5 x 1 5 mm up to max 20 m Cross section 5 x 2 5 mm up to max 40 m Power supply 230Vac 50Hz single phase Connection By fixed wiring and...

Page 22: ...60W timer module ASU2 radio remote control receiver LERN magnetic lock 24Vdc max 1A pedestrian wing with 24Vdc motor with pulser N PE L1 LSI LSA SLA SLZ BT BTG BA BZ __ BS __ VP LSI LSA 8 2kO 8 2kO S...

Page 23: ...ulser for pedestrian wing IMPf pulser See motor Pulser for main wing SU Plug socket Connection for timer module ASU2 Funk Plug socket for receiver EKX1OF or receiver with decoder Integrated receiver f...

Page 24: ...or for one winged gates SCHLOSS 3 pin Connection for electromagnetic bolt or magnetic lock with 24Vdc max 1A WARN 2 pin Potential free contact for warning light 230Vac max 60W MULTI 2 pin Potential fr...

Page 25: ...tton LERN Sequence Function P1 Selection one wing two wings Adjusting of end stops Learning of safety contact profiles and photo cells connected Learning of running distance P2 Adjusting of force and...

Page 26: ...push the button LERN to continue The controller tests the safety contact strips and the photo cells It learns the type of the safety contact strips 8 2 k and the number of connected photo cells Only...

Page 27: ...for minimum speed up to 08 for maximum speed With button LERN the values may be increased with the button BTG they can be decreased Return to the learning sequence using button LERN Attention The max...

Page 28: ...without erasing the code Radio remote control signal Receiving of a learned radio remote control signal is displayed through lighting of the right display dot 8 1 6 Sequence P6 Automatic closure for c...

Page 29: ...ctivated Stay open time 23 seconds 23 Automatic closure is activated Stay open time 123 seconds 2 3 Automatic closure is activated Stay open time 223 seconds Table 16 Return to learning sequence using...

Page 30: ...g button LERN The warning light is only active when a gate wing is moving and during warning prior to opening and closing Display Warning time before opening Warning time before closing 00 No warning...

Page 31: ...esting Prior to every gate movement a photocell test may be performed The test consists of two phases During the first phase the supply of the transmitters is switched off The controller expects withi...

Page 32: ...ing distance P1 After this please check every single photocell for proper function Remark When a faulty photo cell is detected during photo cell testing or when an obstacle is present within the photo...

Page 33: ...A photo cell outside blocks the automatic closure function Only the signal from LSI photo cell inside removes the blocking and starts the stay open time When a vehicle passes through the gate from the...

Page 34: ...itional safety devices like photo cells and safety contact profiles are installed at the gate When sequence PD is activated by button LERN the present selection is displayed With the button BT the val...

Page 35: ...The controller has two integrated detectors with testing function according to EN954 1 category 2 for safety contact profiles with 8 2kOhm resistor for gate OPEN and CLOSE The status of the safety co...

Page 36: ...n OPEN command to the controller The gate cannot be closed as long as the timer is activated After the open time has elapsed the timer sends a CLOSE command to the controller Note When the timer sends...

Page 37: ...failed E4 Testing safety contact profile SLZ failed E5 Running distance exceeded gate was stopped Check end stoppers and re learn the running distance E6 The power supply limit for the external equip...

Page 38: ...s should be used in such a way that the gate can be seen during movement 13 Technical data MO36 13 1 Selection range of Parameter and Original settings Constant not changeable values Parameter Origina...