CONDENSER WATER VALVE ADJUSTMENT

The condenser water valve is factory preset for a condenser water outlet temperature of 95° to 105° F.

If actual temperature varies greatly from this, readjust water flow rate at the valve using the following procedures.

1.

START UP COMPRESSOR

      This can be accomplished by depressing the cooler push button (See Fig. 1 - Item 3).  Keep water running

      during the entire re-adjustment procedure.

2.  

ADJUSTMENT CONDENSER WATER VALVE

       Adjust valve by rotating adjustment stem.  Rotating stem clockwise will decrease water flow.  Counterclockwise

       rotation will increase water flow.  Increasing water flow will result in a lower condenser outlet temperature, while

       decreasing water flow will result in a higher outlet temperature.  Proper adjustment is attained when condenser

       outlet temperature is 95° to 105° F.