1 / 2
HRN-57
HRN-57N
cos φ ≥ 0.95
M
M
HAL.230V
K
M
M
AC12
250V / 1A
DC14
x
AC1
250V / 8A
AC13
x
AC2
250V / 3A
AC14
250V / 3A
AC3
250V / 2A
AC15
250V / 3A
AC5b
300W
DC5
24V / 2A
AC6a
x
DC12
24V / 8A
AC7b
250V / 1A
DC13
24V / 2A
02-10/2017 Rev.: 2
DC1
24V / 8A
DC3
24V / 3A
HRN-57N
15
16 18
N
L2 L3
L1
3~ < U
HRN-57
15
16 18
L2 L3
L1
3~ < U
HRN-57
15 18
16
L2 L3
L1
L1
L2
L3
HRN-57N
15 18
16
L1 N
L2 L3
L1
L2
L3
N
1
3
2
7
4
5
6
Made in Czech Republic
ELKO EP, s.r.o.
Palackého 493
769 01 Holešov, Všetuly
Czech Republic
Tel.: +420 573 514 211
e-mail: elko@elkoep.com
www.elkoep.com
Relay for monitoring over / under voltage
in 3-phase mains
•
it serves to monitor voltage in a switchboard, protection of devices in 3-phase main
•
it monitors value of voltage in 3-phase main
•
relay doesn’t monitor phase sequence
•
it is possible to set upper and lower level independently
•
adjustable time delay eliminated short voltage peaks and failures in the main
•
the device is supplied from monitored voltage
•
faulty state is indicated by red LED and by breaking output relay contact
•
output contact 1x changeover / SPDT 8 A / 250 V AC1
•
in case supply voltage falls below 60 % Un (U
OFF
lower level) relay immediately
breaks with no delay
•
HRN-57
: supply from all phases, means that relay is functional also in case of
failure in one phase
•
HRN-57N
: supply L1, L2, L3-N, means that relay monitors also failure of neutral wire
•
1-MODULE, DIN rail mounting
Characteristics
Description
Symbol
Connection
Type of load
Mat. contacts AgNi,
contact 8A
Type of load
Mat. contacts AgNi,
contact 8A
AC5a
uncompensated
230V / 1.5A (345VA)
AC5a
compensated
x
EN
1. Supply / monitoring terminals
2. Indication
3. Supply indication
4. Adjusting upper value Umax
5. Adjusting of time delay T2
6. Adjusting bottom value Umin
7. Output contact