4 / 4
AirQS-101L
* Values are calculated under ideal conditions and may vary according to alarm frequency
** Depending on network coverage
Power supply
Battery power:
Battery life by frequency *:
1x 10 minutes
1x 60 minutes
1x 12 hours
1x 24 hours
Input
Measurement of CO concentration:
Sensitivity:
Accuracy:
Temperature measuring:
Sensitivity:
Accuracy:
Humidity measuring:
Sensitivity:
Accuracy:
Light intensity measurement:
Range:
Setting
Alarm Detection:
Battery status view:
Button SET:
DIP switch:
Control
Detection area:
Recommended installation height:
Acoustic signal:
Test button SET:
Communication
Protocol:
Transmitter frequency:
Range in open space:
Transmission power (max.):
Other parameters
Humidity:
Working temperature:
Storage temperature:
Operation position:
Mounting:
Protection degree:
Color:
Dimension:
Weight:
battery 4x 1.5 V AA*
2.5 years
3.5 years
3.5 years
3.5 years
YES
0 - 10 000 ppm
5% (0 - 500 ppm)
built-in sensor
-25 .. 110 °C
± 3 °C
built-in sensor
0 .. 90 % RH
± 4 %
built-in sensor
0.045 - 188 000 Lx
message to the server,
indication LED, audible alarm
message to the server,
indication LED
Test / setting / signalling
Position 1 - Turn off scanning signaling
max. 40 m
3
max. 4 m
greater than 85 dB at 3 meters
yes
LoRa
868 MHz
Approx. 10 km**
25 mW / 14 dBm
up to 92% relative humidity (RH) / 10% to 85% RH,
no condensation or frost
0…+40°C (Pay attention to the operating
temperature of batteries)
-30…+70°C
Horizontal (ceiling) / Vertical (Wall)
screws
IP20
white
Ø 120 x 36 mm
184 g (without battery)
Warning
Read the operating instructions before installing the device and putting it into opera-
tion. Instruction manual is designated for mounting and also for user of the device. It is
always a part of its packing. Installation and connection can be carried out only by a per-
son with adequate professional qualifi cation upon understanding this instruction man-
ual and functions of the device, and while observing all valid regulations. Trouble-free
function of the device also depends on transportation, storing and handling. In case you
notice any sign of damage, deformation, malfunction or missing part, do not install this
device and return it to its seller. It is necessary to treat this product and its parts as elec-
tronic waste after its lifetime is terminated. Before starting installation, make sure that all
wires, connected parts or terminals are de-energized. While mounting and servicing ob-
serve safety regulations, norms, directives and professional, and export regulations for
working with electrical devices. Do not touch parts of the device that are energized – life
threat. To ensure the transmission of the radio signal, make sure that the devices in the
building where the installation is installed are correctly located. Unless otherwise stated,
the devices are not intended for installation in outdoor and damp areas, they must not
be installed in metal switchboards or in plastic cabinets with metal doors - this prevents
transmission of the radio frequency signal. iNELS Air is not recommended for control-
ling life-saving instruments or for controlling hazardous devices such as pumps, heaters
without thermostat, lifts, hoists, etc. - radio frequency transmission may be overshad-
owed by obstruction, interference, transmitter battery may be discharged etc., thereby
disabling the remote control.
Technical parameters
The company ELKO EP, as the manufacturer, is entitled to make technical modifi cations to the
product, in the technical specifi cation and product manual, without prior notifi cation.