Technical parameters

A1 - A2

AC 230 V / 50 - 60 Hz

AC max. 14 VA / 2 W

-15 %; +10 %

yes 

automatic 

2x changeover / SPDT (AgSnO

2

)

16 A / AC1*

4000 VA / AC1, 384 W / DC

30 A / < 3 s

250 V AC1 / 24 V DC

> 3x10

7

> 0.7x10

5

up to 3 years 

max. ±1 s per day, at 23 °C (73 °F) 

1 min

10 years at minimum 

100

daily, yearly (until 2099) 

daily, yearly (until 2099)

LCD display, with backlight 

-20.. +55 °C (-4 °F to 131 °F)**

-30.. +70 °C (-22 °F to 158 °F)

4 kV (power supply - output)

any 

DIN rail EN 60715 

IP10 terminals,

IP40 from front panel 

III.

2

solid wire max. 2x 2.5, max. 1x 4 /

with sleeve max. 1x 2.5, max. 2x 1.5

90 x 35.6 x 64 mm (3.5˝ x1.4˝ x 2.5˝)

129 g

 (4.55 oz.) - without battery

EN 61812-1, EN 61010-1

Supply terminals:

Supply voltage:

Consumption:

Supply voltage tolerance:

Real time back-up:

Summer / winter time:

Output

Number of contacts:

Rated current:

Switching capacity:

Peak current:

Switching voltage:

Mechanical life:

Electrical life (AC1):

Time circuit

Real time back-up:

Accuracy:

Minimum interval:

Data stored for:

Program circuit

Number of memory places:

Program:

Interface NFC:

Data readout:

Other information

Operating temperature:

Storage temperature:

Electrical strength:

Operating position:

Mounting:

Protection degree:

Overvoltage category:

Pollution degree:

Max. cable size (mm

2

):

Dimensions:

Weight:

Standards:

Warning 

    

Device is constructed for connection in 1-phase main alternating current voltage and must be 
installed according to  norms valid in the state of application. Connection according to the details 
in this direction. Installation, connection, setting and servicing should be installed by qualifi ed 
electrician staff  only, who has learnt  these instruction and functions of the device. This device 

contains protection against overvoltage peaks and disturbancies in supply. For correct function of 
the protection of this device there must be suitable protections of higher degree (A, B, C) installed 
in front of them. According to standards elimination of disturbancies must be ensured. Before 
installation the main switch must be in position “OFF” and the device should be de-energized. Don´t 
install the device to sources of excessive electro-magnetic interference. By correct installation ensure 
ideal air circulation so in case of permanent operation and higher ambient temperature the maximal 
operating temperature of the device is not exceeded. For installation and setting use screw-driver cca 
2 mm.  The device is fully-electronic - installation should be carried out according to this fact. Non-
problematic function depends also on the way of transportation, storing and handling. In case of any 
signs of destruction, deformation, non-function or missing part, don´t install and claim at your seller it 
is possible to dismount the device after its lifetime, recycle, or store in protective dump.

* When is, switched ON constantly with maximal load 16 A / AC1 and ambient temperature 

55 °C (131 °F) it is highly reccomended by manufacturer to use conductors with tepmerature 
resistive isolation (min) from 105 °C (221 °F) range.

** With temperatures nearing -20 °C (-4 °F), the display quality may be compromised, which does 

not hamper the timer’s function.

Language settings

language 

selection

options 

 - long press (>1s) 

 - short press (<1s)

time/date

options

language

language

Control description 

entrance into programming menu

browsing in menu

setting of values 

quick shifting during setting of 
values

entrance into required menu

confi rmation 

one level up 

a step back

back to the starting menu

Device diff ers short and long button press. 
In the manual marked as:

 - short button press (< 1s)
 - long button press (> 1s)

After 30s of inactivity (from the last press of any button) will device automatically returns into 
starting menu.

Battery replacement 

You can change the battery without disassembling the device.

CAUTION  
- only change the battery when the device is disconnected from power supply!!!
- the date and time must be reset after changing the battery!!!

- remove the plug-in module with the battery
- replace the original battery
- enter a new battery so that its upper edge (+) lines up with the plug-in module
- slide the plug-in module in the device and pay attention to polarity (+ up) - for roughly 1 s, the 

display will show the name and the software version 

- you can connect the device to power supply

All manuals and user guides at all-guides.com

Summary of Contents for SHT-7

Page 1: ...olling the individual output relays manually Options of the automatic switching programme Time programme switching based on a pre set time programme Memory capacity for 100 time programmes common for both channels Programming can be performed both when power is on or in backup mode Output relays only operate with a supply voltage of AC 230 V Menu display selection CZ SK EN ES PL HU RU default fact...

Page 2: ...st be in position OFF and the device should be de energized Don t install the device to sources of excessive electro magnetic interference By correct installation ensure ideal air circulation so in case of permanent operation and higher ambient temperature the maximal operating temperature of the device is not exceeded For installation and setting use screw driver cca 2 mm The device is fully elec...

Page 3: ... the summer and winter time depending on area setting the week day date format time format time date time hour minute time date year month day date su wi su wi week day date form 16 sep 10 16 sep 10 16 sep 10 week day date form time form time form 12h 24h end Prog no su wi su wi rus Prog su wi usa Prog Prog su wi eur Time program By shortly pressing OK you can toggle between the program number and...

Page 4: ...ode setting the end of the holiday mode holiday on inactive manual manual end channel channel choosing the channel manual mode switching on the manual mode Setting the switching modes Time correction The shift unit is 0 1s per day The numeric value refers to seconds per 10 days Time correction is factory set and individual for each product so that the real time clock would run with minimum deviati...

Reviews: