background image

8/12 

 

INSTALLATION 

 
 

A

A

A

A

A

Clip for
front panel
opening

Clip for
front panel
opening

Hole for
wires

Hole for
wires

Clip for
front panel
opening

Clip for
front panel
opening

Hole for
wires

Fasten
hole

Fasten
hole

Hole for
wires

Fasten
hole

Fasten
hole

 

 

Rear view 

 
Fix the addressable device by following the instructions reported below: 

  Remove the cover from the device by acting on the clips. 

  In the wires access used M20 Cable/Tube Gland. 

  Install  on  a  wall  by  using  the  relevant  fixing  holes  placed  on  the  bottom  of  the  enclosure  (as 

illustrated in the picture). 

  Connect the device TM24I according to the schematic illustrated in the picture. 

 

 

Important:  connect  the  end  of  line  resistor,  used  for  supervising  the  connection  between  the 
control  panel  and  type  “C”  fire  alarm  devices,  to  the  OUT  terminal  block  of  the  last  device 
connected to the fire alarm signalling circuit. The value of the end of line resistor is indicated in 
the documentation of the fire detection control panel. 

 

 

Insert the 2 provided rubber blocks, as illustrated in the picture, on the retention hooks with lower 
protrusion; close the cover to the device by observing the alignment arrows

 

Secure the cover with the provided screws.

 

  Apply the supplied stickers on the four clips for front panel opening and the side hole for wires, 

indicated with “A”. 

 
How to replace the pictographs into the device: 

  Remove the cover from the device by acting on the clips; 

  Remove the transparent part from the cover by acting on the clips; 

  Insert  the  desired  pictograph  between  the  transparent  part  and 

the cover; 

 

Re-assemble  the  transparent  part  on  the  cover  and  insert  the  2 
provided  rubber  blocks,  as  illustrated  in  the  picture,  on  the 
retention  hooks  with  lower  protrusion;  close  the  cover  to  the 
device by observing the alignment arrows

 

Secure the cover with the provided screws.

 

 

 
 
 
 

 

Summary of Contents for TM24I

Page 1: ...rivelazione TM24I pu anche essere utilizzato come segnalatore non collegato sulla linea di rivelazione ma alimentato e gestito da una uscita di segnalazione allarme incendio uscita sirena di una centr...

Page 2: ...DS 5 Posizione DS 6 Posizione Modalit acustica di allarme OFF OFF Modo 1 sweep in frequenza da 800 970Hz per 1s ON OFF Modo 2 tono alternato a 610Hz per 0 5s e 920Hz per 0 5s OFF ON Modo 3 tono interm...

Page 3: ...itivi di segnalazione allarme di tipo C sull ultimo dispositivo presente sulla linea sirena ai morsetti OUT Il valore del resistore di fine linea indicato sulla documentazione della centrale di rileva...

Page 4: ...ATTERISTICHE TECNICHE Tensione di funzionamento 20Vcc 15 10 modulata linea rivelazione 24Vcc 15 10 uscita segnalazione allarme incendio Assorbimento in condizioni normali 250 A 20Vcc Assorbimento in c...

Page 5: ...in loco del comportamento mezzi speciali richiesti impostazioni marcate chiaramente Livello di pressione acustica LpA 65 dB A LpA valore dichiarato in tutti gli angoli misurati Frequenze e modelli son...

Page 6: ...ADDRESSING AND PROGRAMMING The address of the device 1 128 is configured via software by using the fire detection control panel with automatic or manual procedure The address is internally stored in...

Page 7: ...0 5s OFF ON ON Tone 4 continuous 920Hz DS 7 Position Initial synchronization of alarm activation ON Initial activation synchronized with other devices on the same circuit OFF Initial activation non s...

Page 8: ...st device connected to the fire alarm signalling circuit The value of the end of line resistor is indicated in the documentation of the fire detection control panel Insert the 2 provided rubber blocks...

Page 9: ...e detection control panel TECHNICAL SPECIFICATIONS Operating voltage 20Vdc 15 10 modulated detection circuit 24Vdc 15 10 fire alarm signalling circuit Power consumption in normal condition 250 A 20Vdc...

Page 10: ...anufacturer s adjustment special means required On site adjustment of behaviour special means required setting clearly marked Sound pressure level LpA 65 dB A LpA declared value at all measured angles...

Page 11: ...RCUIT LA LA LB LB CENTRALE LINEA RIVELAZIONE CONTROL PANEL DETECTION CIRCUIT SCHERMO SHIELD IN IN OUT OUT TM24I SCHERMO SHIELD IN IN OUT OUT TM24I SCHERMO SHIELD IN IN OUT OUT TM24I SCHERMO SHIELD IN...

Page 12: ...solatore chiuso Icmax Maximum rated continuous current with the switch closed Icmax 100mA Massima corrente di commutazione Ismax Maximum rated switching current Ismax 180mA Massima corrente di perdita...

Reviews: